Boiler is

cold,

house is

cold

Display is ON;

TT-LED is ON

B1 LED is ON

120 Vac at B1-

B2

If no, replace control.

If yes, check burner

and wiring

Display is ON;

TT-LED is ON

Refer to err on

display

Boiler is

hot, house

is cold

Display is ON;

TT-LED is ON

C1 LED is ON

120 Vac at C1-

C2

120 Vac at C1-C2,

check wiring to pump

Wiring ok, is pump

running? If not,

replace the pump.

If pump is running,

check for trapped air

or closed zone

valves.

Display is ON;

TT-LED is ON

C1 LED is OFF;
ZC LED is ON

b

Boiler below the

Low Limit

temperature,

wait for boiler to

go above Low

Limit

temperature.

Display is ON;

TT-LED is ON

ZC LED is
OFF

c

Boiler above

LL? If yes,

check for 120

Vac between ZC

and L2

If no 120 Vac,

replace control.

If yes, check zone

relays, circulators

and wiring.

Table 3. Troubleshooting Guide

a

.

System

Condition

Diagnostic

Condition

Check

Action

a

. Refer to Fig. 5 for Display and LED locations.

b

. ZC LED ON indicates ZC terminal power is OFF.

c

. ZC LED OFF indicates ZC terminal power is ON.