Calibration

THERMOSTAT

T874 Thermostats are accurately calibrated at the factory.

They do not have provision for field calibration.

THERMOMETER

The thermometer in the thermostat has been accurately

calibrated at the factory. The thermometer should need ad-
justment only if it has been dropped or shifted due to mishan-
dling.

If the set point lever and the thermometer reading do not

agree, use the following procedure:

1. Remove the thermostat cover by pulling up from the

bottom of the cover until it clears the mounting slots.

2. Set the thermostat cover on a table near an accurate

thermometer.

3. Allow ten minutes for cover thermometer to sense area

temperature; compare the readings. Be careful not to touch
the thermometer or breathe on it.

4. If the readings are the same, replace cover and put the

system into operation.

5. If the readings are different, insert a small screwdriver

in the thermometer slot (Fig. 24) and turn it until the ther-
mometers have the same reading.

6. Replace thermostat cover and put the system into

operation.

NOTE: Hand heat will offset the thermometer reading.

After making each adjustment, wait ten minutes for the
thermometer to stabilize before comparing.

Fig. 24—Thermometer calibration.