Caution, Settings – Honeywell Q674A-E User Manual

Page 9

Advertising
background image

9

60-1165—6

9. Firmly tighten the mounting screw.

10. If the HEAT and COOL levers are to be locked in

place at a specific temperature, use the two insulated head
screws supplied instead of the two adjustable lever stop
brackets.

CAUTION

Do not use standard screws that provide metal-to-
metal contact with the stop brackets. Short circuit
and potential equipment damage may result.

Fig. 19—Installing brass insert.

LED WINDOW

BRASS INSERT

INSERT HOLE

BACK OF
THERMOSTAT

M955A

Fig. 20—Installing stop brackets.

MOUNTING THE THERMOSTAT

1. Remove the thermostat cover by pulling the bottom

edge of the cover upward until it snaps free of the cover clip.

NOTE: The cover is hinged at the top and must be removed

by pulling up at the bottom.

2. Carefully remove and discard the polystyrene packing

insert that protects the mercury switches during shipment.

3. Turn over the thermostat base and note the spring

fingers that engage the subbase contacts. Make sure the
spring fingers are NOT bent flat, preventing proper electri-
cal contact with the subbase.

4. Set the adjustable heat anticipator indicators to the

respective current setting for each stage. See Setting the
Heat Anticipator section.

5. Note the two tabs on the top inside edge of the

thermostat base. The tabs fit into corresponding slots on top
of the subbase. Mount the thermostat on the subbase.

6. Align the two captive mounting screws in the ther-

mostat base with the posts on the subbase. See Fig. 21.
Tighten both screws. Do not overtighten screws or damage
to subbase posts can result.

Fig. 21—Mounting thermostat on subbase.

Settings

SETTING THE HEAT ANTICIPATOR

Move the indicator to match the current rating of the

primary contro. See Fig. 22. When using the T874 Thermo-
stat with two stages of heating, set each heat anticipator to
match its respective primary control current draw. If you
cannot find the current rating on the primary control, or if
further adjustment is necessary, see NOTE and use the
following procedure to determine the current draw of each
stage.

The current draw must be measured with the thermostat

removed from the subbase and the power on to the heating
system.

1. Connect an ac ammeter of appropriate range between

the heating terminals of the subbase:

Stage 1: between W1 and RH or R.
Stage 2: between W2 and RH or R.

HEAT
LEVER

HOLES FOR INSULATED
LOCKING LEVER SCREWS

COOL
LEVER

HOLE WITH
BRASS INSERT

BRACKET
TABS

ADJUSTABLE
LEVER STOP
BRACKETS

BRACKET
SLOTS

MOUNTING
SCREW

M18682