Event log, Show events – Home Automation HOME AUTOMATION User Manual

Page 46

Advertising
background image

The next series of displays shows the current analog reading for each security zone input. The displays show the readings for
zones 1-48.

1=147 2=148 3=147

4=146 5=146 6=147


THROUGH

43=148 44=147 45=147

46=145 47=149 48=146


Normal readings for zones are between 137 - 157 when secure. If Zones 1-4 are configured as Fire or Gas zone, normal readings
are between 26 - 43 when secure. Each reading should be changing only by two or three counts from its average steady reading.
When a door or window is opened, the reading will go up to a value that represents that zone is open.

This feature can be used to monitor the quality of the zone wiring and contacts. If the numbers begin to deviate from their
original values when the system was new, wiring problems that will eventually lead to trouble or false alarms may be developing.
You may wish to record the Status Test values for future reference.

5 = TEMP (TEMPERATURE)


The Temperature Status menu allows you to view and scroll through the status of each Thermostat, PESM, and Temperature
Sensor. To enter the Temperature menu, from the Status menu, press the 5 key on the console keypad. The system will display:

TSTAT 1 TEMP:80

HEAT:60 COOL:82


You may enter a unit number to start displaying the status with that unit, or simply press the down arrow key to scroll through the
list of temperature zones. The status display is as shown under Temperature Control, except that now the arrow keys may be used
to continue scrolling.

TSTAT

1

MODE: AUTO FAN: AUTO


At this point, you may press the ' # ' key to control the temperature zone as specified under Temperature Control.

6= ENERGY (ENERGY COST)


The Energy Cost Status menu allows you to view the current energy rate in use.

ENERGY

COST:

MID


The Energy Cost will display Lo, Mid, Hi or Crit (for critical) energy rates.

Event Log


The Event Log records the 250 most recent significant security system Events (happenings) and trouble conditions in the system.
When a new event occurs, the oldest one is lost.

The following Events, along with the time and date of their occurrence are recorded in the Event Log when they occur:

All Security system Armings and disarmings (Off, Day, Night, Away, and Vacation), and user name.

All zones bypassed or restored by the user, and user name.

Any zone automatically bypassed by the system.

Any zone tripped while the security system is armed.

Any trouble condition (zone, battery, fuse, AC power, or phone).

The restoration of any trouble condition (the trouble condition ceased to occur).

Any Remote Telephone Access, Remote Access Denied, or Remote PC Access.