13

BURNER FEATURES

201 gas burner characteristics

Gas category

Type

Heating

Hot water

Input

Kw

60 - 220

60 - 240

Nominal output

Kw

56.4 - 200.2

56.4 - 218.4

Combustion efficiency - natural gas

%

96.6 - 91.5

96.6 - 91.5

Natural gas CO

2

%

9

9

Pressure loss of the flue-gas circuit

mbar

2.4

2.9

Net T° of combusted gases

°C

180

190

Mass flow rate of combustion products

g/sec.

110.3

120.3

Gas G20 - 20 mbar -

I 2E(R)B - I 2 Er - I 2H - I 2E - I 2ELL

Flow

m

3

/h

6.35 - 23.28

6.35 - 25.40

Gas G25 - 20 mbar -

I 2ELL /

25 mbar -

I 2L

Flow

m

3

/h

7.38 - 27.08

7.38 - 29.54

Gas G31 - 30/37/50 mbar -

I 3P

Flow

m

3

/h

2.45 - 9.00

2.45 - 9.81

CO

2

%

11.0 - 11.2

11.0 - 11.2

BG 2000-M/201

Tube

Gas valve

Ignition electrode

Ø 5/4” gas supply
flange

Flame inspection window

Fan

Venturi

Burner adjustment
(Prohibited in Belgium).

With the burner operating at full
power, the CO

2

must be in the

range 8.8 to 9.2 % (natural gas)
or 10.5 to 10.6 % (propane).

If necessary, adjust the CO

2

by

turning the screw clockwise to
reduce it and counter-clockwise
to increase it.

(see photo

opposite)

.

Increase

Reduce