Mcba for specialists: installer, service engineer – Heatmaster 201 User Manual

Page 21

Advertising
background image

19

MCBA FOR SPECIALISTS:

INSTALLER, SERVICE ENGINEER

Heating lock time (sec x 10.2)

STEP

Hot water lock time (sec x 10.2)

STEP

Lock time to switch from hot water mode to heating mode (sec x
10.2)

STEP

Difference T1 - T2 for modulation

STEP

BUS address (-1 = disabled)

STEP

Increase the primary temperature value to generate hot water
(relative to the hot water temperature)

STEP

1st digit: heating circuit (AM3-11 – 4-way valve)
0 = disabled

5 = enabled

2nd digit: the demand for heat comes from:
0 = room thermostat

STEP

00

00

00

05

- 01

05

00

Key

Display

Description of the parameters

Factory setting

1st digit: Hot water circulator pump (= 1)

2nd digit: tank with NTC3 sensor (= 2)

STEP

Manual fan speed (- 01 = modulation)

12

- 01

11

00

60

30

01

00

STEP

1st digit: PWM pump operating speed

2nd digit: PWM pump speed during time-delay

STEP

Holding temperature

STEP

Maximum temperature for the heating circuit outlet
(AM3-11 – 4-way valve)

STEP

Minimum temperature for the heating circuit outlet
(AM3-11 – 4-way valve)

STEP

Hysteresis of the heating circuit outlet temperature
(AM3-11 – 4-way valve)

STEP

1st digit: Special pump (0 = disabled)

2nd digit: Minimum disable cycle (0 = disabled)

STEP