Termination locations, Warning, A. vent termination minimum clearances – Heat & Glo Fireplace TIARAP-CES User Manual

Page 8

Advertising
background image

Page 8

August 1, 2008

Heat & Glo · Tiara Petite B · 7026-101K

4

Termination Locations

A. Vent Termination Minimum Clearances

Gas

Termination

Wood & Fuel Oil

Termination

Comments

A

6 in.

20 in. min.

Horizontal distance between terminations

B

20 in.

24 in. min.

Distance to perpendicular wall

C

18 in.

18 in.

Vertical distance between terminations

C

A

GAS

TERMINATION

B

GAS, WOOD OR FUEL

OIL TERMINATION

Figure 4.2 Multiple Vertical Temination

Figure 4.1 Termination Clearances

Figure 4.3 specifi es minimum vent heights for various
pitched roofs.

Figure 4.3 Minimum Height from Roof to Lowest Discharge

HORIZONTAL

OVERHANG

VERTICAL

WALL

GAS DIRECT VENT
TERMINATION CAP

12

X

ROOF PITCH

IS X/ 12

LOWEST

DISCHARGE

OPENING

2 FT.

MIN.

20 INCHES MIN.

H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING

Roof Pitch

H (Min.) Ft.

Flat to 6/12 ......................................................... 1.0*
Over 6/12 to 7/12

........................................................ 1.25*

Over 7/12 to 8/12 ............................................... 1.5*
Over 8/12 to 9/12 ............................................... 2.0*
Over 9/12 to 10/12 ............................................. 2.5*
Over 10/12 to 11/12 ........................................... 3.25
Over 11/12 to 12/12 ........................................... 4.0
Over 12/12 to 14/12 ........................................... 5.0
Over 14/12 to 16/12 ........................................... 6.0
Over 16/12 to 18/12 ........................................... 7.0
Over 18/12 to 20/12 ........................................... 7.5
Over 20/12 to 21/12 ........................................... 8.0

* 3 foot minimum in snow regions

Measure vertical clearances from this surface.

Measure horizontal clearances from this surface.

(See

Figure 4.4 for specifi c clearances.)

Opening

Fire Risk.

Explosion Risk.

Maintain vent clearance to combustibles
as specifi ed.

WARNING

• Do not pack air space with insulation or

other materials.

Failure to keep insulation or other materials
away from vent pipe may cause fi re.

Advertising