Hubbell Fire Pump Controller LX-1500 User Manual

Page 8

Advertising
background image

Limited Service Fire Pump Controller

Page 8 of 12

11. Press the STOP push button to stop the motor.

12. Start and stop the motor with the EMERGENCY MANUAL CONTROL handle. Push and

rotate the T-handle in a quick motion to lock the contactor in the ON position to start.
Rotate the T-handle clockwise and release to stop the motor.

Caution:

Failure to engage the handle in a fast and continuous motion can

result in damage to the contactor and failure to start the motor.

If equipped with an LX-250 or LX-350 Automatic Transfer Switch, complete the following
additional tests:

1. Verify connection of the engine generator set start wires to TB-1 and TB-2 at the top of the

LX-250 Transfer Switch power panel or to TB8-1 and TB8–2 on the left side of the LX-350
Transfer Switch power panel.

2. Close the

FIRE PUMP

(emergency)

ISOLATING SWITCH

and open the CIRCUIT

BREAKER. The Automatic Transfer Switch should transfer to the alternate source per
system requirements. Bump the motor to check for proper rotation. If incorrect, move the

FIRE PUMP ISOLATING SWITCH

to the OFF position and switch the generator set off using

the switch located on the generator. Switch any two leads on the line side of the

FIRE PUMP

ISOLATING SWITCH

. Return the generator set control switch to the Auto position and close

the

FIRE PUMP ISOLATING SWITCH

. The generator set may start.

3. Operate the pump on the alternate (emergency) source using the START and STOP push

buttons.

4. Close the CIRCUIT BREAKER. The Control Module should now be sensing normal power

and timing for retransfer. Press the

BYPASS RETRANSFER TO NORMAL

push button to

return the Transfer Switch to the normal position.