Mount horizontally on reinforced duct, Mount horizontally on vertical duct, Wiring – Honeywell HE420A User Manual

Page 4: Plumbing humidifier, Caution

Advertising
background image

HE420A STEAM POWER HUMIDIFIER

68-0192—4

4

1. Position the bracket 1/2 in. (13 mm) from the edge of the

duct and trace around the bracket. See Fig. 5.

2. Once the outline has been traced, remove bracket.

3. Drill a 3/8 in. (10 mm) hole within the center portion of

the bracket.

4. Use tin snips to cut around the outline of the bracket.

IMPORTANT

Follow the dotted line carefully.

5. Remove the sheet metal.

Fig. 5. Position bracket.

6. Use two 8-32 screws and nuts to attach the mounting

bracket (L shaped with six holes) to the top/ front surface

of the humidifier. The humidifier is now ready for mounting.

NOTE: Position the humidifier so the upward protrusion of the

U is on the side toward the reservoir.

IMPORTANT

Do not mount the humidifier until the water level is

adjusted. See Set The Water Level section.

7. Slide the flanges of the humidifier reservoir into the

mounting bracket until the reservoir’s front flange comes

in contact with the edge of the duct.

8. Secure the humidifier to the duct with three no. 8 sheet

metal screws.

Mount Horizontally on Reinforced Duct

This horizontal mounting method usually requires duct

reinforcement to support the weight of the humidifier and keep

it level. See Fig. 3. The mounting bracket is not used.

1. Position the bracket to the bottom of the duct in the

desired location.

2. Once the outline has been traced, remove bracket.

3. Drill a 3/8 in. hole (10 mm) within the center portion of

the shaded area.

4. Use tin snips to cut around the outline of the bracket.

IMPORTANT

Follow the dotted line carefully.

5. Remove sheet metal.

IMPORTANT

Do not mount the humidifier until the water level is

adjusted. See the Set The Water Level section.

6. Slide the flanges of the humidifier reservoir into the

mounting bracket.

7. Secure the humidifier to the duct with two no. 8 sheet

metal screws.

Mount Horizontally on Vertical Duct

Horizontal mounting on a vertical duct requires the installation

of a duct extension. See Fig. 4. Additional duct reinforcement

may also be necessary to help support the weight of the

humidifier and keep it level.

Create and install the duct extension. Then follow steps 1

through 8 in the Mount Horizontally Using Mounting Bracket

section to complete installation.

WIRING

All wiring must comply with local codes and ordinances. For

complete wiring instructions, refer to the manual “Wiring

Instructions for High-Capacity Steam Humidifiers” packaged

with your HE420A humidifier.

PLUMBING HUMIDIFIER

CAUTION

Chemical Hazard.

Can cause damage to environment or air

conditioning system.

Do not use any refrigerant line connected to an air

conditioner. Be sure to install the chlorine removal filter

(provided) to prevent humidifier corrosion.

Either hard or soft water can be used in the humidifier.

IMPORTANT

Use only copper tubing to plumb the humidifier.

1. Locate the cold water pipe closest to the humidifier.

2. Install the saddle valve connector.

3. Use the valve instructions to install the valve (provided).

The valve is self-piercing when installed on copper pipe.

IMPORTANT

Position the valve so water flows from the top or side to

reduce the chance of clogging the valve with minerals.

Lightly clean the copper tubing ends with fine sandpa-

per before making any connections.

4. Install the chlorine removal filter.

5. Place the brass compression nut over the copper tubing.

6. Slide the brass ferrule over the tubing.

NOTE: Do not overtighten the compression nut.

Moderate tightness prevents leaking.

7. Insert the tubing into the valve fitting and tighten the

compression nut.

M23374

BRACKET

1/2 IN. (13 MM)
FROM EDGE

Advertising