HE420A STEAM POWER HUMIDIFIER

7

68-0192—4

11. Reset the water level.

CAUTION

Flooding Hazard.

Inadequate support of the float arm can lead to

valve seat damage resulting in water leakage.

Support the float arm during adjustment.

a. Set the humidifier reservoir on a level surface.

b. Attach the water feed line and allow the unit to fill

until the float valve shuts off the incoming flow of

water. The water level should be between 2-1/4 in.

(57 mm) and 2-1/2 in. (64 mm) deep. If water level is

correct, go to step d.

c. Adjust the water level in small increments. Raise the

water level by pushing down on the center of the

float arm. Lower the water level by pressing the float

down with one hand and pulling up on the center of

the float arm with the other hand. See Fig. 6.

d. Verify the water level by removing enough water to

allow the float valve to automatically fill and shut off

the water.

12. Remount the humidifier.

13. Reconnect all plumbing connections.

14. Reconnect all electrical connections.

15. Verify humidifier operation by following the steps in the

Checkout Procedures section.

End of Humidification Season

Clean and shut off the humidifier at the end of the heating

season. Use the Every 1 To 4 Months section, steps 1 through

14, to shut down for the season.

IMPORTANT

Be sure the humidifier power is off and there is no

water in the humidifier.

Vacation

When you leave on vacation, turn off the humidifier water

supply and the humidity control. When you return, turn on the

humidifier water supply and reset the humidity control to restart

the humidifier.

CHECKOUT PROCEDURES

After winter start-up or maintenance, use the following

procedure to check humidifier operation:

1. Turn on the humidifier water supply.

2. Be sure the humidifier has power and plug in the humidifier.

3. Turn the Automatic Humidity Control to the Test position.

NOTE: If relative humidity is above 45% in the home, or the

outdoor temperature is above 50°F, a jumper may

need to be placed across the humidistat’s OUT termi-

nals to perform this checkout.

4. Check that the furnace blower turns on to circulate the

moist air. The blower may take as long as fifteen minutes

to turn on.

5. Reset the Automatic Humidity Control to the desired dial

setting for automatic operation.

TROUBLESHOOTING

Refer to Table 4 for troubleshooting procedures.

Table 4. Troubleshooting Procedures.

Problem

What To Look For

What To Do

Low humidity

Humidifier heater is not operating.

Confirm that humidifier is plugged in.

Set the humidistat higher.

Check for low water level.

Reset circuit breaker or check for blown fuse.

Check that the furnace power is on.

Check all external wiring connections.

Check the humidity control setting.

Call a professional heating contractor.

Rapid air changes. Drafts (cold air is dry

and is an added load for the humidifier).

Keep doors and windows closed.

Close fireplace damper when not in use.

Keep exhaust fan running time to a minimum.

Seal around doors and windows.

High humidity

Condensation on walls.

Turn off humidity control and water until condensation is

completely evaporated.

Heavy condensation on windows.

Turn humidity control down low enough to eliminate

condensation caused by moisture from bathing, mopping,

cooking, etc. If moisture persists, more ventilation is

needed.