Heatcraft Refrigeration Products Condensing Units H-IM-CU User Manual

Page 4

Advertising
background image



Requirements for Remote and Water Cooled

Condensing Units

General Installation

The indoor compressor units are designed to be used with a remote

condenser. The water cooled units are similar, except that they have an

integral water cooled condenser. Inlet and outlet water connections are to

be made in the field. On units having a compressor water jacket, incoming

water shall be routed through the jacket prior to entering the condenser. For

cleaning purposes, condenser end plates can be removed to give access to

the water tubes. Cleaning is accomplished by a simple spiral tool powered

by an ordinary electric drill. During installation, allow space for cleaning the

condenser. Commercial equipment of this type is intended for installation

by qualified refrigeration mechanics.

Typical Arrangements

Diagram 1 illustrates a typical piping arrangement involving a remote

condenser located at a higher elevation, as commonly encountered when

the condenser is on a roof and the compressor and receiver are on grade

level or in a basement equipment room.

In this case, the design of the discharge line is very critical. If properly sized

for full load condition, the gas velocity might be too low at reduced loads

to carry oil up through the discharge line and condenser coil. Reducing the

discharge line size would increase the gas velocity sufficiently at reduced

load conditions; however, when operating at full load, the line would be

greatly undersized, and thereby creating an excessive refrigerant pressure

drop. This condition can be overcome in one of two of the following ways:

The discharge line may be properly sized for the desired pressure

drop at full load conditions and an oil separator installed at the

bottom of the trap in the discharge line from the compressor.

1.

City & Tower Water Connections

In the refrigeration industry “City” and “Tower” are designations of

temperature and flow conditions, not applications. The term “City” refers

to operating conditions where incoming water is 75˚F, and condensing

temperature is 105˚F. “Tower” refers to a higher temperature relationship

which is normally 85˚F, incoming water and 105˚F condensing temperature.
Water circuits in some condenser models provide a center, or Tower, outlet

connection to allow divided inlet water flow. This extra water port reduces

water velocity, water pressure drop, and condenser wear in applications such

as cooling towers where higher inlet temperatures and water flows occur.

Water Connections for City

For City water (open system) high pressure applications, the Tower

connections is plugged.

Water Connections for Tower

For Tower usage and low pressure applications, both normal water

connections will be used as inlets and the tower connection as an outlet.

Diagram 1

Diagram 2

Figure 2. Water Connections

A double riser discharge line may be used as shown in

Diagram 2. Line “A” should be sized to carry the oil at minimum

load conditions and the line “B” should be sized so that at the

full load conditions both lines would have sufficient flow velocity

to carry the oil to the condenser.

Water Regulating Valve

Using this control on the water cooled condensing units, the head pressure

can be maintained by adjusting the flow of water through the condenser

section. This type control is most often located on the water entering side of

the condenser and is regulated by the refrigerant condensing pressure.

Subcooler

Diagrams 1 and 2 below show typical subcooler piping. Diagram 1 is the

preferred connection with receiver as it provides maximum subcooling.

Diagram 2 may be used if the receiver is located far from the condenser.
Notes:

All oil traps are to be as short in radius as possible. Common practice is

to fabricate the trap using three 90 degree ells.
Pressure relief valves are recommended at the condenser for protection

of the coil.
A pressure valve at the high point in the discharge line is recommended

to aid in removing non-condensables.
The placement of a subcooler should be that it does not interfere with

normal airflow of the condenser. Increased static of the unit could cause

a decrease in system capacity and fan motor damage.

2.

1.

2.

3.

4.

Advertising