Mounting thermostat on subbase – Honeywell 2000 User Manual

Page 8

Advertising
background image

62-0135

8

Q7300A,C,D,G SERIES 2000 COMMERCIAL THERMOSTAT SUBBASES

Home and Building Control
Honeywell Limited-Honeywell Limitée
155 Gordon Baker Road
North York, Ontario
M2H 2C9

62-0135 J.H. Rev. 12-96

Fig. 17. Typical hookup of T7300D,F/Q7300G in three-stage heat and three-stage cool conventional system.

Mounting Thermostat on Subbase

Mount the thermostat on the subbase after the subbase is
installed.

³

Engage tabs at the top of the thermostat and
subbase. Fig. 18.

·

Press lower edge of case to latch.

NOTE:

To remove the thermostat from the wall,
first pull out at the bottom of the thermo-
stat; then remove the top.

IMPORTANT

Refer to the thermostat installation instructions for
Installer Setup, Settings, Installer Self-Test and
Troubleshooting information.

Fig. 18 Mounting thermostat on subbase.

M4824A

B.

PRESS LOWER EDGE OF CASE TO LATCH.

A.

ENGAGE TABS AT TOP OF THERMOSTAT AND SUBBASE OR WALLPLATE.

Home and Building Control
Honeywell Inc.
Honeywell Plaza
P.O. Box 524
Minneapolis, MN 55408-0524

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

JUMPER RC TERMINAL TO RH TERMINAL WHEN INSTALLED ON A SYSTEM WITH ONE TRANSFORMER.

USE A1 AND A2 WHEN THE CONTACTS SHOULD BE NORMALLY CLOSED IN OCCUPIED MODE. USE A2 AND A3 WHEN CONTACTS
SHOULD BE NORMALLY OPEN IN OCCUPIED MODE.

CONNECT GND TO EARTH GROUND.

INSTALL FIELD JUMPER BETWEEN X4 AND X TO POWER LEDS.

USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.

1

1

1

4

6

M4949A

2

2

3

4

5

6

3

5

HEAT
RELAY 3

W2

L1
(HOT)

L2

FAN
RELAY

Y1

G

X

SUBBASE

RC

RH

C1

T

T7147 REMOTE COMFORT ADJUST MODULE

GND

W1

C2

L1
(HOT)

L2

COMPRESSOR
CONTACTOR 1

C4

C3

C5

CA1

T

CA2

CA4

CA3

CA5

T

T

Y2

COMPRESSOR
CONTACTOR 2

HEATING
TRANSFORMER

COOLING
TRANSFORMER

W3

Y3

HEAT
RELAY 2

COMPRESSOR
CONTACTOR 3

A2 A3

A1

X3

X1

X4

EQUIPMENT

MONITOR 2

EQUIPMENT

MONITOR 1

ECONOMIZER

AS

AS

DISCHARGE
AIR
SENSOR

HEAT
RELAY 1

www.honeywell.com/building/components

Advertising