Honeywell CT8602C User Manual

Page 2

Advertising
background image

69-0446—2

2

Fig. 2—Mounting wallplate on wall.

Fig. 4—CT8602C heating-only circuit in a
continuous pilot gas system.

Fig. 6—CT8602C heating/cooling circuit in a
single transformer system with gas heat and
electric cooling or electric heat and electric
cooling, RC and R terminals.

L1
(HOT)

L2

1

1

Y

RC

R

G

W

FAN RELAY

24V

WALLPLATE

M121A

FACTORY-
INSTALLED
JUMPER

GAS
VALVE

POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.

Fig. 5—CT8602C heating-only circuit in an oil
system.

L1
(HOT)

L2

1

1

Y

RC

R

G

W

T

T

OIL PRIMARY

M122

WALLPLATE

POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.

FACTORY-
INSTALLED
JUMPER

WIRES THROUGH
WALL OPENING

WALL

WALL
ANCHORS
(2)

WALLPLATE

MOUNTING
HOLES (3)

MOUNTING
SCREWS (2)

USE TWO MOUNTING HOLES THAT
BEST FIT APPLICATION.

1

1

M2917

WIRING

All wiring must comply with local electrical codes and

ordinances.

Disconnect power before wiring to prevent electrical

shock or equipment damage.

The shape of the terminal barrier permits insertion of

straight or conventional wraparound wiring connections.
Either method is acceptable.

Refer to Table 1 and Fig. 4 through 8 for wiring guide-

lines.

NOTE: Keep all wiring restricted to ribbed area surrounding

terminals (Fig. 3) to assure thermostat/wallplate contact.

TABLE 1—TERMINAL CROSS REFERENCE.

FOR STRAIGHT
INSERTION –
STRIP 5/16 in. [8 mm]

FOR WRAPAROUND –
STRIP 7/16 in. [11 mm]

RESTRICT
WIRING TO
THIS AREA

WIRING TO BE BELOW
THIS SURFACE

TOP SURFACE
OF SUBBASE

FRONT VIEW OF

TERMINAL AREA

CROSS-SECTIONAL VIEW OF

TERMINAL AREA

M2927

Fig. 3—Keep wiring restricted to ribbed area
surrounding terminals.

Old Thermostat

Terminal Marked

Function

New Thermostat

Terminal Marked

G or F

Fan

G

Y or C

Cooling

Y

W or H

Heating

W

RC, V, VC or R

Power

RC

RH, M, VR, 4

Power

R

L2

1

2

2

1

Y

RC

R

G

W

24V

M119

L1
(HOT)

COOLING
CONTACTOR

HEATING
PRIMARY
CONTROL

FAN RELAY

WALLPLATE

POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.

PRIMARY CONTROL SUCH AS GAS VALVE OR
ELECTRONIC IGNITION MODULE.

FACTORY-
INSTALLED
JUMPER