Honeywell Chronotherm IV T8602C User Manual

Page 6

Advertising
background image

69-1567

6

T8602C CHRONOTHERM

®

IV DELUXE PROGRAMMABLE THERMOSTATS

Table 3. Thermostat Installer Setup Options.

Installer Setup

Number (Press

Time

Factory-Setting

Other Choices

(Press

or

key to change)

Actual

Select

key to change)

Display

Description

Display

Description

Setting

Not used.

1

Fan operation

a.

2

0

Conventional applica-
tions where equipment
controls fan operation
in heat mode.

1

Heat pump or electric heat
applications where thermostat
controls fan operation in heat
mode.

Not used.

3

Heating cycle
rate.

4

6

6—6 cph used for

conventional heat.

1, 3 or
9

1—1 cph used for radiant floor

heat, gravity system.

3—3 cph used for hot water

systems or high efficiency
furnaces.

9—9 cph used for electric

heat systems.

Not used.

5 thru 12

Adaptive
Intelligent
Recovery™
control.

13

1

Conventional recovery
(system starts
recovery at
programmed time).

0

Adaptive Intelligent
Recovery™ control is
activated (system starts early
so setpoint is reached by start
of program period).

Not used.

14 and 15

Clock format.

16

0

12-hour clock format.

1

24-hour clock format.

Not used.

17 thru 23

Outdoor
temperature
display (select
models).

24

0

No outdoor
temperature is
displayed.

1

Outdoor temperature is
displayed. Needs a
C7089B1000 Outdoor Sensor
to operate.

Not used.

25 thru 32

Minimum off
time for the
compressor.

33

5

5 minute minimum off
time for the
compressor.

0 thru 4 Minimum number of minutes

(0 thru 5) the compressor will
be off between calls for the
compressor.

Temperature
range stops in
heating.

34

32.0

Highest setting for
heating setpoint.

4.5 to
31.5

Temperature range (0.5°C
increments) heating setpoint
can be set to.

Temperature
range stops in
cooling.

35

7.0

Lowest setting for
cooling setpoint.

7.5 to
37.0

Temperature range (0.5°C
increments) cooling setpoint
can be set to.

Not used.

36

Temperature
display
adjustment.

37

0

No difference in
displayed temperature
and actual room
temperature.

1.5 thru
-1.5

.5—Display adjusts to 0.5°C

higher than actual room
temperature.

1.0—Display adjusts to 1.0°C

higher than actual room
temperature.

1.5—Display adjusts to 1.5°C

higher than actual room
temperature.

-.5—Display adjusts to -0.5°C

lower than actual room
temperature.

-1.0—Display adjusts to -1.0°C

lower than actual room
temperature.

-1.5—Display adjusts to -1.5°C

lower than actual room
temperature.

a

Number 2 must be set to 1 to extend fan operation.