Caution, Vent information and diagrams, Warning – Heat & Glo Fireplace MTL-INSERT User Manual

Page 9

Advertising
background image

9

Heat & Glo • MTL-Insert • 2145-900 Rev. G • 6/09

CAUTION

ALL vent specifi cations MUST be followed.

• This product is tested and listed to these specifi cations.

• Appliance performance will suffer if specifi cations are not

followed.

EXHAUST VENT PIPE

TERMINATION CAP

ADAPTOR

INSULATION SEAL

INLET VENT AIR PIPE

MIN. = 14FT.
MAX. = 50FT.

Figure 5.1

C. Measuring Standards

Vertical measurements listed in the vent diagram (Figure
5.1) were made using the following standard:

• Vertical terminations are measured to top of chimney.

Fire Hazard.

Explosion Risk.

Asphyxiation Risk.

Do NOT connect this gas appliance to a
chimney fl ue serving a separate solid fuel or
gas burning appliance.

• May impair safe operation of this appliance

or other appliances connected to the fl ue.

• Vent this appliance directly outside.

• Use separate vent system for this appliance.

B. Horizontal Venting

Horizontal venting is NOT allowed.

5

5

Vent Information and Diagrams

A. Vent Table Key

The abbreviations listed in this vent table key are used in
the vent diagrams.

Symbol

Description

V

MIN

Minimum Vertical Run Length 14 ft.

V

MAX

Maximum Vertical Run Length 50 ft.