SOLID CORE AND SPLIT CORE ADJUSTABLE CURRENT “STATUS” SWITCHES

62-0242—01

2

Fig. 2. Sensor removed from DIN rail

Fig. 3. Wires through sensors

WARNING

The secondary of the 5 Amps Current
Transformer must be shorted together before
the power may be turned on to the monitored
device.

For applications in which the normal operating current is
greater than 250 Amps or for conductor diameters larger
that 3/4 in. (19 mm) in diameter, and external 5 Amps
Current Transformer (C.T.) must be used as shown in
Fig. 4.

Fig. 4. Current transformer

Latch Operation

Pressing down on the two (2) side tabs and swinging the
cover open opens the split core current switch as shown
in Fig. 5. Lifting up the latch with a flat-tip screwdriver as
shown in Fig. 6 can also open the unit. Press down firmly
on the cover to close the current switch. An audible “click
will be heard as the tab slides over the tongue on the
base.

CAUTION

Mating surfaces of the magnetic core are
exposed when the sensor is open. Silicone
grease, present on the cores to prevent rust,
can capture grit and dirt if care is not
exercised. Operation can be impaired if
anything prevents good contact between pole
pieces. Visually check the mating parts of the
core before closing the current sensor.

Fig. 5. Opening sensor by hand

3X

M25290

C

R

U

L

U

S

M25291

U

R

C

L

US

U

R

C

L

US

EXAMPLE: FOR CURRENTS UP TO 600 AMPS, USE A 600:5 RATIO C.T.

AS

SHOWN.

INSULATED CONDUCTOR

600:5 RATIO 5A C.T.

WIRE NUT

M25295A