SOLID CORE AND SPLIT CORE ADJUSTABLE CURRENT “STATUS” SWITCHES

3

62-0242—01

Fig. 6. Opening with a screwdriver

Wiring

Honeywell recommends the use of a 2 conductor 16 to
22 AWG (1.3 to 0.3 mm

2

) shielded cable or twisted wire,

copper wire only, for all current switch output applications.
A maximum wire length of less than 98.4 feet (30 meters)
should be used between the current switches and the
Building Management System or controller.

NOTE: When using a shielded cable, be sure to connect

only (1) end of the shield to ground at the con-
troller. Connecting both ends of the shield to the
ground may cause a ground loop.

When removing the shield from the sensor end, make
sure to properly trim the shield so as to prevent any
chance of shorting. The current switch output terminals
represent a solid-state switch for controlling AC and DC
loads and is not polarity sensitive. The recommended
torque to be used on the terminal block connections is
5.93 in-lbs. (0.67 Nm). The aperture (hole) size of the
current switch is 3/4 in. (19 mm) and will accept a
maximum cable diameter of 350 MCM (17.3 mm). See
Fig. 7 for use as a digital input to a building management
system and Fig. 8 for use as a pilot relay application.

OPERATING SPECIFICATIONS

Max Sensing Current Voltage: 600 Vac

Table 1. Specifications by Product Number.

Fig. 7. Digital circuit

Fig. 8. Analog circuit

M25299

C

US

R

U

L

Product Number

Core
Type

Normal

Position

Adjustable

Trip Point

Output Switch

Rating

Max. Current

Cont.

Max. Current

for 6 secs.

Max. Current

for 1 sec.

CSS-O-A300-001

Solid

N.O.

1.0-250 Amps

0.30 Amps @
200 Vac/Vdc

250 Amps

500 Amps

1,000 Amps

CSS-O-A200-001

Solid

N.O.

0.50-250 Amps 0.30 Amps @

200 Vac/Vdc

250 Amps

500 Amps

1,000 Amps

CSS-C-A300-001

Solid

N.C.

1.0-250 Amps

0.15 Amps @
300 Vac/Vdc

250 Amps

500 Amps

1,000 Amps

CSP-O-A300-001

Split

N.O.

3.0-200 Amps

0.30 Amps @
200 Vac/Vdc

200 Amps

400 Amps

800 Amps

CSP-O-A200-001

Split

N.O.

2.0-200 Amps

0.30 Amps @
200 Vac/Vdc

200 Amps

400 Amps

800 Amps

CSP-C-A300-001

Split

N.C.

3.0-250 Amps

0.15 Amps @
300 Vac/Vdc

250 Amps

500 Amps

1,000 Amps

CSP-C-A200-001

Split

N.C.

2.5-250 Amps

0.15 Amps @
300 Vac/Vdc

250 Amps

500 Amps

1,000 Amps

DIGITAL INPUT #1

BUILDING MANAGEMENT

SYSTEM

M25302

RELAY

CONDITIONER

24 VAC COIL

120 VAC

LINE

DI

(STATUS)

M23933

DDC CONTROLLER

DO

(RELAY COIL OR

CONTACTOR)

24 VAC COIL

TRANSFORMER