Mounting the thermostat – Honeywell MULTISTAGETHERMOSTATSAND T874H User Manual

Page 6

Advertising
background image

69-0087—6

6

T874H,Q,W MULTISTAGE THERMOSTATS AND Q674B,C,G,L SUBBASES

Fig. 9. T874W/Q674L for three-stage heat and two-stage cool with outdoor reset.

1

T

W3

G

R

E

X1

C

B

O

X2

Y1

Y2

C815A OUTDOOR
THERMISTOR

AUX. HT. RELAY

FAN RELAY

EM. HT. RELAY

CHANGEOVER
RELAY (HEAT)

CHANGEOVER
RELAY (COOL)

COMPRESSOR
CONTACTOR 1

COMPRESSOR
CONTACTOR 2

EM.HT.

AUTO

ON

FAN SWITCH

H1 ANTICIPATOR

H2 ANTICIPATOR

H3 ANTICIPATOR

RESET

FALL

FALL

FALL

H1

H3

H2

AUX. HEAT
LED (GREEN)

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

CONNECT CHANGEOVER RELAY TO 'O' TERMINAL FOR CHANGEOVER IN COOLING OR TO 'B' TERMINAL FOR CHANGEOVER IN HEATING.

M6999

C1 ANTICIPATOR

RISE

RISE

C2 ANTICIPATOR

C1

C2

EM. HEAT
LED (RED)

CHECK LED
(YELLOW)

HEAT

OFF

COOL

SYSTEM

SWITCH

2

2

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1

2

3

4

5

6

8

9

10

11

12

L1
(HOT)

L2

1

Mounting the Thermostat

³

Remove the thermostat cover by pulling the bottom
edge of the cover upward until it snaps free of the
cover clip.

NOTE:

The cover is hinged at the top and must be
removed by pulling up at the bottom.

·

Carefully remove and discard the polystyrene
packing insert that protects the mercury switches
during shipment.

»

Turn over the thermostat base and note the spring
fingers that engage the subbase contacts. Make
sure the spring fingers are

not

bent flat, preventing

proper electrical contact with the subbase.

¿

T874Q only: Set the heat anticipator indicators to
the respective current setting for each stage. See
Setting the Heat Anticipator section. T874H and
T874W have fixed anticipation; the settings are
preselected and cannot be adjusted.

´

Note the tabs along the top inside edge of the
thermostat base. The tabs fit into the subbase
notches. Mount the thermostat base on the subbase
and tighten the captive mounting screws. See Fig. 1.

²

Place the upper edge of the thermostat cover on the
thermostat base and swing the cover downward until
it engages with the cover clip on the base.

Advertising