T874H,Q,W MULTISTAGE THERMOSTATS AND Q674B,C,G,L SUBBASES

THERMISTOR RESISTANCE

C815A THERMISTOR RESISTANCE
R = 400 ohms ± 10% AT 77°F (25°C)

4600
4400
4200
4000
3800
3600
3400
3200
3000
2800
2600
2400
2200
2000
1800
1600
1400
1200
1000

800
600
400
200

0

-20 0 20 40 60 80 100 120 140

TEMPERATURE OF THERMISTOR (°F)

M1590A

SETTING

Setting the Heat Anticipator (T874Q Only)

Set each heat anticipator to match its primary control
current draw. If the primary control nameplate has no
rating or if further adjustment is necessary, use the
following procedure to determine the current draw of each
stage. (Measure the current draw of each heating stage
with the thermostat removed and the power on.)

³

Connect an ac ammeter of appropriate range
between the heating terminals of the subbase as
follows:

Stage 1: between W1 and RH or R.
Stage 2: between W2 and R.

·

Move the system switch to AUTO (if applicable).

»

After one minute, read the ammeter and record the
reading.

¿

After mounting the thermostat, set the adjustable
heat anticipator(s) to match the respective
reading(s) measured in step

»

.

Temperature Setting

Move the heating and cooling levers to the desired
positions. The minimum differential between the heating
and cooling setpoints is 3

°

F (1.7

°

C), which means the

setting levers cannot be set closer together than 3

°

F

(1.7

°

C) (5

°

F [2.8

°

C] for T874W).

Subbase Setting

System switching positions control thermostat operation as
follows:

OFF: Both the heating and cooling systems are off. If

the fan switch is in the AUTO position, the cooling
fan is also off.

AUTO: Thermostat automatically changes between the

heat and cool modes, depending on the indoor
temperature.

HEAT: Heating system is controlled by the thermostat.

Cooling system is off.

EM. HT.: Emergency heat relay is energized. The

cooling system is off. When the compressor has
failed and the heat pump is not operating, switch to
the EM. HT. position.

Fan switching positions control fan operation as follows
(Q674B,C, or L):

ON: Fan operates continuously.
AUTO: Fan operates with cooling equipment as

controlled by the thermostat or with the heating
equipment as controlled by the plenum switch.

To switch positions, use thumb and index finger to slide
the lever to the desired position. The switch lever must
stop in detent over the desired function indicator mark for
proper circuit operation.

C815 Outdoor Reset Thermistor (T874W only)

The T874W is used with a C815 Thermistor mounted in
the outdoor section. The thermistor must be used; if not,
thermostat performance will deviate radically from proper
operation.

Fig. 10 Thermistor resistance chart.

The proper thermistor operation must be verified to assure
the correct operation of the thermostat. Check the
thermistor operation as follows:

³

Disconnect the

T wire on the subbase.

·

Use an ohmmeter to measure resistance between
the

T

wire and the transformer common.

»

Take the outdoor temperature at thermistor location
and find the correct thermistor resistance on the
chart in Fig. 10.

¿

If the resistance measured in step

·

and the

calculated resistance in step

»

vary by more than

15 percent, the thermistor requires replacement.
Contact the installing dealer for the packaged
replacement outdoor thermistor.

CHECKOUT

Heating

Move the system switch on the Q674 Subbase to HEAT or
AUTO. Move the heating lever on the T874 about 10

°

F

(6

°

C) above room temperature. Both stages of heating

start and the fan runs after a short delay. Move the heating
lever about 10

°

F (6

°

C) below room temperature. The

heating equipment shuts off, and the fan runs for a short
time, and then shuts off.

Cooling

Move the system switch on the Q674 Subbase to COOL
or AUTO. Move the cooling lever on the T874 Thermostat
about 10

°

F (6

°

C) below room temperature. The cooling

equipment and fan start. Move the cooling lever about
10

°

F (6

°

C) above room temperature. The cooling equip-

ment and fan stop.

Emergency Heat

Move the system switch to EM. HT. The EM. HT. LED
comes on. Move the heating lever about 10

°

F (6

°

C) above

room temperature. The electric strip heater(s) comes on.
Move the heating lever about 10

°

F (6

°

C) below room

temperature. The electric strip heater de-energizes. The
EM. HT. LED remains on until the system switch is moved
to another postion.