Install expandapac media filter, Checkout, Maintenance – Honeywell EXPANDAPAC F35F User Manual

Page 8

Advertising
background image

F35F Expandapac™ MEDIA AIR CLEANER

68-0178—2

8

Fig.15. Insert combs in media filter.

M6935

COMBS (3 OR 4,
DEPENDING ON
FILTER SIZE)

Fig. 14. Assemble Expandapac media filter in frame.

Install Expandapac Media Filter

Slide the assembled Expandapac media filter into the cabinet,
making sure the arrow on the cartridge points in the direction
of the airflow.

Replace the access door. Insert the tab on the bottom of the
door into the slot in the cabinet. Swing the door closed and
press it into place.

M6934

END PANEL
TAB

END PANEL
FLANGE

FRAME PANEL

RETAINER

FRAME
PANEL

FRAME
PANEL

FRAME

FLANGE

Checkout

Visually check the installation. Make sure:

Airflow is in the direction of the arrow on the
Expandapac media air filter.

Turning vanes and transitions, if used, are properly
installed.

Joints in sheet metal between media air cleaner and
furnace are sealed.

All sheet metal connections are complete.

Original furnace filter was removed and blower
compartment was cleaned.

Replace any access doors removed during the Installation or
Checkout.

Run the furnace or cooling system through one complete
cycle to make sure the system operates as desired.

Maintenance

Replace the media filter when pressure drop across the
media filter reaches 0.5 in. wc (0.1 kPa) or at least annually. If
the media air filter is installed downstream from an atomizing
humidifier or if the installation includes both heating and
cooling, more frequent replacement may be necessary.
Clogged media filter must be replaced promptly to avoid
restricting airflow and reducing efficiency of the heating-
cooling system. Record the replacement date in the space
provided on the replacement media filter.

Replace the Expandapac Media Filter as follows:

1. Remove the cabinet door and pull out the dirty filter

assembly.

2. Remove all the combs and two frame panels. Set them

aside. Dispose of the dirty filter.

3. Open the new media filter; expand it and set it upright

on a flat surface.

4. Insert one end panel tab into the retainers on the frame.

Fold in the end panel flanges and push the tab
completely in, making sure the end panel flanges are
inside the frame flanges. See Fig. 15.

5. Repeat step 4 on the opposite corner.

6. Flip over the assembly and repeat steps 4 and 5 on the

remaining two corners.

7. Lay the filter assembly down flat so the arrows point up.

Insert the combs as shown in Fig.16, aligning them with
the notches in the end panel flanges. Make sure the
combs are inserted completely.

8. Insert the new filter assembly into the cabinet and close

the door.

See Replacement Parts in the Specifications section. If desired,
install the S830A Clogged Filter Indicator to allow visual
indication of when the media needs replacing. Install and adjust
the S830A by following the instructions provided with the unit.

Advertising