Honeywell GES User Manual

Page 3

Advertising
background image

DN-6872 • 12/19/02 — Page 3 of 3

GE Series Wiring with AVS44 Sync Module

GEC Models
Conventional
Wiring

GEH/GES Models
Conventional
Wiring

6872wirc2.wmf

6872wirc1.wmf

6872wirs.wmf

Horn Ratings over Input Voltage Range of 16 – 33 V

Horn Mode

dBA @ 10' (3.048 m)

per UL 464

HIGH dB

dBA @ 10' (3.048 m)

per UL 464

LOW dB

DC (mA)

FWR (mA)

16 V

24 V

33 V

16 V

24 V

33 V

16 V

24 V

33 V

16 V

24 V

33 V

Temporal 3 2400 Hz

78

83

84

71*

75

77

13

19

24

27

37

43

Temporal 3 Mechanical

76

81

82

70*

73*

76

11

16

22

23

33

40

Temporal 3 Chime

70*

71*

71*

66*

68*

70*

9

12

15

19

24

29

Continuous 2400 Hz

81

86

87

74*

78

80

14

21

28

21

42

48

Continuous Mechanical

80

84

85

72*

76

78

13

18

25

27

37

44

Continuous Chime

70*

71*

73*

66*

68*

70*

10

12

15

19

24

30

Whoop

82

83

83

69*

72*

75

43

51

56

51

58

62

6872horn.tbl

TABLE NOTES: 1) *Operating the horn in this mode at this voltage will not meet the minimum UL reverberant sound level
required for public mode fire protective service. These settings are acceptable only for private mode fire alarm use. Use the high
dBA setting for public mode application (not applicable when using the chime tone — the chime tone is always private mode).
2) The sound output for the temporal 3 tone is rated lower, as the time the horn is off is averaged into the sound output rating.
While the horn is producing a tone in the temporal 3 mode, its sound pressure is the same as when in continuous mode.

Advertising
This manual is related to the following products:

GEH, GEC