Step 3 installing the vent system, A. vent system approvals, Figure 4. vent components and terminations – Hearth and Home Technologies CFX-Crescent User Manual

Page 13

Advertising
background image

Heat & Glo • CFX-CRESCENT • 705-900 Rev. P • 12/07

13

Figure 4. Vent Components and Terminations

Vent System

Termination Kits

Vent System Components

A. Vent System Approvals

This model is approved to use SL-series direct vent pipe com-
ponents and terminations (as indicated in this guide), and mod-
el AK-CFX air kits. Approved vent system components are la-
beled for identification. This pipe is tested and listed as an ap-
proved component of the fireplace. The pipe is tested to be run
inside an enclosed wall. There is NO requirement for inspection
openings at each joint within the wall. There is no required pitch
for horizontal vent runs. This model is not approved for use
with SLK-01D termination cap. NO OTHER VENTING SYS-
TEMS OR COMPONENTS MAY BE USED
.

Detailed

installation instructions are included with each vent termina-

tion kit and should be used in conjunction with this Installers Guide.
Drawing below shows vent system components and terminations.

Step 3
Installing the
Vent System

!

SLK-991DA

SLK-01TRD

HORIZONTAL
TERMINATION

WALL FIRESTOP

90 DEGREE
ELBOW

VERTICAL
TERMINATION

STORM COLLAR

ROOF FLASHING

HORIZONTAL PIPE
SUPPORT

PIPE LENGTH

WALL BRACKET

CEILING
FIRESTOP

COMBUSTION

AIR DUCT COLLAR

NOTE: SLK-01D is NOT

approved for use.

NOTE: When installing the AK-CFX outside air kit, it is normally not necessary
to install the air intake cap on the same wall as the exhaust termination cap.
However, installations involving tall buildings or areas subjected to frequent high
winds, it is recommended that the air intake cap be installed on the same wall
as the exhaust termination cap.

Identifying Vent Components

The vent systems installed on this gas fireplace may include up to eight 90°

elbow

assemblies. The relationships of vertical rise to horizontal run in vent configurations
using 90° elbows MUST BE strictly adhered to. The rise to run relationships are shown
in the venting drawings and tables. Refer to the diagrams on the next several pages.

NOTE: TWO 45° ELBOWS MAY BE USED IN PLACE OF ONE 90° ELBOW.
RISE TO RUN RATIOS IN THE VENT SYSTEM MUST BE FOLLOWED IF 45°
ELBOWS ARE USED.

WARNING: THIS UNIT IS DESIGNED TO OPERATE USING OUTSIDE COM-
BUSTION AIR. IT IS MANDATORY TO INSTALL AN AK-CFX AIR KIT USING
4-INCH INSULATED DUCTING. THE 4-INCH (102MM) DUCT COLLAR FOR
THE AIR KIT WILL COME MOUNTED TO THE FIREPLACE. SEE FIGURE 6.