4 input/output group [i/o – HP 30 HP30 User Manual

Page 70

Advertising
background image

Chapter 5 - Parameter List

5-10

Keypad Display

Setting Range

Code

Description

LCD

7-Segment

LCD

7-Segment

Units

Factory

Default

Adj.

During

Run

Page

FU2-94

Parameter Write
Protection

Para. Lock

94

0 to 255

1

0

Yes

6-2

FU2-99 Return Code

Not

displayed

99

Not available

[PROG/ENT]

or

[SHIFT/ESC]

- 1 Yes

6-2

5.4 Input/Output Group [I/O]

Keypad Display

Setting Range

Code

Description

LCD

7-Segment

LCD

7-Segment

Units

Factory

Default

Adj.

During

Run

Page

I/O-00 Jump to Desired Code #

Jump code

Not displayed

1 to 84

Not available

1

1

Yes

6-2

I/O-01

Filtering Time Constant for
V1 Signal Input

V1 filter

01

0 to 10000 [ms]

1

10 [ms]

Yes

I/O-02 V1 Input Minimum Voltage

V1 volt x1

02

0 to 10 [V]

0.01

0.00 [V]

Yes

I/O-03

Frequency Corresponding
to V1 Input Minimum
Voltage

V1 freq y1

03

0 to FU1-20

0.01

0.00 {Hz}

Yes

I/O-04 V1 Input Maximum Voltage

V1 volt x2

04

0 to 10 [V]

0.01

10.00 [V]

Yes

I/O-05

Frequency Corresponding
to V1 Input Maximum
Voltage

V1 freq y2

05

0 to FU1-20

0.01 60.00 [Hz] Yes

6-2

I/O-06

Filtering Time Constant for
I Signal Input

I filter

06

0 to 10000 [ms]

1

10 [ms]

Yes

I/O-07 I Input Minimum Current

I curr x1

07

0 to 20 [mA]

0.01 4.00 [mA]

Yes

I/O-08

Frequency Corresponding
to I Input Minimum Current

I freq y1

08

0 to FU1-20

0.01

0.00 [Hz]

Yes

6-2

I/O-09 I Input Maximum Current

I curr x2

09

0 to 20 [mA]

0.01 20.00 [mA] Yes

I/O-10

Frequency Corresponding
to I Input Maximum
Current

I freq y2

10

0 to FU1-20

0.01 60.00 [Hz] Yes

6-2

None 0

half x1

1

I/O-11

Criteria for Analog Input
Signal Loss

Wire broken

11

below x1

2

- None Yes

6-2

Speed-L 0

Speed-M 1

Speed-H 2

XCEL-L 3

XCEL-M 4

XCEL-H 5

Dc-brake 6

2nd Func

7

Exchange 8

I/O-12 Multi-Function Input

Terminal ‘P1’ Define

P1 define

12

- Reserved -

9

- Speed-L Yes

6-2