69-1481-1 G.H. Rev. 2-02

Printed in U.S.A.

www.honeywell.com/yourhome

T8411R ELECTRONIC HEAT PUMP THERMOSTAT

Automation and Control Solutions

Honeywell

Honeywell Limited-Honeywell Limitée

1985 Douglas Drive North

35 Dynamic Drive

Golden Valley, MN 55422

Scarborough, Ontario
M1V 4Z9

5. Press the ▼ key to change the °C or °F indication.

NOTE: Stage-one heat and cool cycle rates are fixed at

3 cph. Only stage-two heat cycle rates are

selectable.

6. Press the ▲ key to display the heat cycle rate of 3,

4, 5, 6, 9 or 12. If the desired cycle is displayed,

see Table 1, press the ▲ key to exit the installer
setup mode. To change the heat cycle rate, press

the ▼ key to scroll between 3, 4, 5, 6, 9, and 12.
Stop scrolling when the desired rate is displayed.

a

High efficiency furnace.

b

Refer to equipment manufacturer’s instructions.

7. Press the ▲ key to display cooling algorithm con-

figuration default.

8. Press the ▲ key again to change cooling algorithm

to C1 or C3.

C1 = Standard cooling algorithm.

C3 = Aggressive cooling algorithm (can cause

overshooting).

9. Press the ▲ key again. Current configuration (CC)

is displayed. A typical example is shown, but CC

varies by model. (This information is for factory use
only.)

10. Press the ▲ key to save all changes, exit installer

setup mode and return to normal operation.

NOTE: After exiting installer setup mode, change the

setpoint to the desired room temperature.

CHECKOUT

Heating

1. Slide the SYSTEM switch to Heat and the FAN

switch to Auto.

2. Press and hold the ▲ key to raise the temperature

setting several degrees above the room tempera-

ture. After approximately five minutes, the heating
equipment should start.

3. Press the ▼ key to lower the temperature setting

below the room temperature. Heating equipment

should stop.

Cooling

CAUTION

Equipment Damage Hazard.

Operating at too low of an outdoor
temperature may cause compressor damage.

Do not operate cooling if outdoor temperature is
below 50°F (10°C). Refer to manufacturer’s

recommendations.

• For compressor protection, allow the

compressor to remain off for five minutes
before restarting.

1. Slide the SYSTEM switch to Cool and the FAN

switch to Auto.

2. Press the ▼ key to lower the temperature setting

several degrees below the room temperature. After
approximately five minutes, the cooling equipment

and fan should start.

3. Press the ▲ key to raise the temperature setting

above the room temperature. Cooling system
should shut down.

Fan

1. Slide the SYSTEM switch to Off and the FAN

switch to On. The fan should run continuously.

2. Slide the FAN switch to Auto. The system turns the

fan on and off with the equipment.

Make certain all equipment responds properly to the
thermostat.

Table 1. Heat Cycle Rates.

System

Cycles per Hour

Hydronic heat, condensing gas
furnace

a

3

Gas or oil forced air

6

Electric heat

9

Special applications

b

4, 5, 12

M14689

M14690

M18421

or

M18420