9

4.5 Installer Parameters Table
4.5.1 Category 1 - Room Thermostat Settings

Notes
1) Remember to always press the green button to confirm that you want to store your new Installer Set-

Up setting. To exit the Installer Mode move the slider switch to the AuTO or MAN position.

Parameter

Parameter

No.

Factory Default Setting

Optional Setting

Category 1 Parameters – Room Thermostat Settings

Display

Description

Display Description

AM-PM / 24hr
Display

1:CL

24

24 hr clock display
format

12

12 hr – AM/PM clock display format

Reset Time/ Temp
Program

2:rP

1

Time / Temp profile set
to factory default

Changes to 0 when
one of the time/temp
profiles are changed

0

Time / Temperature are as programmed

To restore the factory profile set to 1

Auto Summer/
Winter Time
Change

3:tC

1

Auto Summer/Winter
Time Change Enabled

0

Auto Summer/Winter Time Change
Disabled

LCD Backlighting

5:bL

1

Backlighting Enable

0

Backlighting Disabled

Upper Temp Limit

6:uL

35

35°C Upper Temp.
Limit

21 to

34

21°C to 34°C adjustment in 1°C steps

Lower Temp Limit

7:LL

5

5°C Lower Temp. Limit

5 to 21

6°C to 21°C adjustment in 1°C steps

Optimisation

8:OP

0

Optimisation Disabled

1

Optimisation Enabled

Temperature Offset

12:tO

0

No temperature offset

-3 to

+3

-3°C to +3°C adjustment in 0.1°C steps

Proportional Band
Width

13:Pb

1.5

Proportional band of
1.5 degrees

1.6 to

3.0

1.6°C to 3.0°C adjustment in 0.1°C steps

Reset Parameters
to Factory Defaults

19:FS

1

All settings at factory
defaults

Changes to 0 when
one of the parameter
is changed

0

Settings are as modified above

To restore the factory profile set to 1