CM900 Wireless - Programmable Room Thermostat

4.5.2 Category 2 - System Settings

Notes
1) Remember to always press the green button to confirm that you want to store your new Installer Set-

Up setting. To exit the Installer Mode move the slider switch to the AuTO or MAN position.

2) These parameters are set centrally for the zoning system at the room thermostat configured as the

system synchroniser.

3) Minimum on-time setting applies only to the boiler controller. All receiver box zone controllers will work

with the minimum on-time of 30 seconds.

Parameter

Parameter

No.

Factory Default Setting

Optional Setting

Category 2 Parameters – System Settings (press the

button to access this category)

Display

Description

Display Description

Minimum boiler
ON time

1:Ot

1

1 minute minimum
ON time

2 to 5

Selection of 2, 3, 4 or 5 minutes
minimum ON time

Cycle Rate

2:Cr

6

6 cycles per hour
(cph)

3,9 or

12

Selection of 3, 9 or 12 cph

Heat/Cool Change

4:HC

0

Disabled

1

Enabled

Pump Exercise

5:PE

0

Pump exercise
disabled

1

Pump exercise enabled

System
Synchronisation

6:Sn

0

Standard operation of
the Room Unit

1

Room unit configured as Synchroniser

Loss of
Communications
Instruction

7:LC

0

Relay Off

1

Relay 20% on / 80% off

The following Parameters are for the control of other Honeywell Wireless products such as Wireless Underfloor Heating
controls and Wireless Radiator controls. For more information please contact Honeywell sales.

Room Temperature
Sensor Use

8:Su

0

HC60 control

1,2,3

or 4

1 - HR80/HM80 control with own/remote
sensor (no temperature displayed)
2 - Hr80/HM80/HCE80 control with CM
sensor
3 - HC60 control and HR80/HM80/
HCE80 control with own/remote sensor
4 – Hr80/HM80/HCE80 control with own/
remote sensor (temperature displayed)

HR80 Window-
Open Function

9:HO

0

Disabled

1

Enabled

HR80 Local
Override

10:HL

1

Enabled

0

Disabled

Maximum Flow
Setpoint

11:uF

55

55°C Maximum Flow
Temp.

0 to 99

0°C to 99°C adjustment in 1°C steps

Minimum Flow
Setpoint

12:LF

15

15°C Minimum Flow
Temp.

0 to 50

0°C to 50°C adjustment in 1°C steps

Mixing Value Run
Time

13:Ar

150

150 seconds

0 to
240

0 to 240 sec. adjustment in 1sec steps

Pump Overrun Run
Time

14:Pr

15

15 minutes

0 to 99

0 to 99 mins adjustment in 1min steps