Common problems and solutions, Symptom common causes possible corrections – Honeywell Series 4 User Manual

Page 11

Advertising
background image

Part number 550-141-893/0800

11

AHE Series 4 Direct Vent Wall-Mounted Boilers — User’s Information Manual

Common problems and solutions

Symptom

Common Causes

Possible Corrections

Rapid cycling —
boiler turns on and
off frequently

Thermostat installed where drafts
or heat affect reading

Locate thermostat on inner wall away from heat sources or cool
drafts.

Heat anticipator in thermostat
adjusted incorrectly

Adjust thermostat per manufacturer's instructions.

Incorrect limit setting

Set limit according to system needs. Maximum setting is 220˚F.
Increase limit setting to decrease cycling.

Insufficient water flow through
boiler

Check all valves to and from boiler. Return to proper setting.

Confirm circulator size.

Frequent release of
water through relief
valve

Expansion tank sized too small

Call qualified service technician to check expansion tank
operation and size.

Flooded expansion tank

Call qualified service technician to check expansion tank
operation.

Inoperative limit control

Call qualified service technician to replace limit control.

Need to frequently
add makeup water

Leaks in boiler or piping

Have qualified service technician repair leaks at once to avoid
constant use of makeup water. Makeup water can cause
mineral deposits which, in turn, can cause boiler section failure.
Do not use petroleum-based stop-leak compounds.

Black water
condition

Oxygen corrosion due to leaks in
boiler and piping

Have qualified service technician repair at once. Keep pH of
water between 7.0 to 8.5.

Popping or
percolating noise
heard in boiler

Mineral deposits in sections due
to constant use of makeup water

Call qualified service technician to de-lime boiler, if necessary.
In some cases, deposits will be too heavy to remove with de-
liming procedures.

Have qualified service technician repair leaks to eliminate need
for constant makeup water.

Incorrect pH of boiler water

Call qualified service technician to check pH level and correct.
pH should be maintained between 7.0 to 8.5.

Insufficient water flow through
boiler

Check all valves to and from boiler. Return to proper setting.

Confirm circulator size.

Metal flakes found in
vent outlet or vent —
flueway corrosion

Contaminated combustion air
supply — See page 4 in this
manual.

Remove any contaminating products. See page 3 in this
manual.

Provide outside air for combustion. Kit available through Weil-
McLain distributor. Have qualified service technician pipe-up kit.

Condensation of combustion
gases in boiler sections

Have qualified service technician inspect system piping and
controls to verify proper regulation of return water temperature.

Some radiators or
baseboard units do
not heat or are noisy

Air in system

Bleed air from system through air vents in radiators or
baseboard units.

Low system pressure

Fill to correct pressure.

Check for leaks in boiler or piping. Have qualified service
technician repair at once.

High limit set too low

Adjust high limit to higher setting.