Heating – Honeywell MAGICSTAT 3355 User Manual

Page 28

Advertising
background image

28

69-1012

Step 10: Check Thermostat Operation after Programming and Installing

Heating

Do

not check heating system

operation by jumpering thermostat
terminals at the primary control
such as the gas valve, zone valve,
or oil burner control. This damages
the thermostat, instead, jumper R
and W wires at the thermostat.

Move the system switch to HEAT
and the fan switch to AUTO.

Press key until the setting is about
10

°

F (6

°

C) above room tempera-

ture. Heating should start and the
fan should run after a short delay
(immediately if fan operation switch
is set in E position).

Press key until setting is about 10

°

F

(6

°

C) below room temperature. The

heating equipment should shut off.

Heat

Cool

Off

Auto

On

Warmer

Cooler

Advertising