System defaults – Heatcraft Refrigeration Products BEACON II SMART CONTROLLER H-IM-80C User Manual

Page 15

Advertising
background image

15

SYSTEM DEFAULTS
Following are factory defaults for the parameters which can be programmed in
the Beacon II Smart Controller. If the user does not select a setting for any of
the following parameters, the default will be used.

It is important the user set ALL parameters based of their needs.

PARAMETERS

CODE

AIR

ELECTRIC

Refrigerant

REFTYP

R22

R404A

Box Temperature

BOXTMP

35

°

F

-10

°

F

Superheat

SUPRHT

8

°

F

8

°

F

Smart Defrost

SMTDEF

N/A

Off**

Defrost start times

DEF ST

9 AM/9 PM

4 AM, 10 AM, 4 PM, 10 PM

Defrost Fail-safe time

DEFSAF

40 min

30 min

(60 min. when Smart Defrost is On)

Defrost End Temperature

DEFTMP

45

°

F

60

°

F

(55

°

F when Smart Defrost is On)

Alarm High Temperature

ALR HI

50

°

F

5

°

F

Alarm Low Temperature

ALR LO

30

°

F

-15

°

F

Alarm Time

ALRMIN

60 min

60 min

Temperature Units

°

F /

°

C

°

F

°

F

Clock setting

12 / 24H

12 H

12 H

Test mode

TEST

Off

Off

Service mode

SERVIC

Off

Off

**When Smart Defrost is turned on, 8 defrost periods per day will automatically be

programmed. These will be at 12:00 am, 3:00 am, 6:00 am, 9:00 am, 12:00 pm, 3:00
pm, 6:00 pm, and 9:00 pm. Also, the defrost fail safe time will be set to 60 minutes,
and the defrost termination temperature will be set to 55

°

F. The user can change

these as needed for the application (for version 1.2).

System Defaults