8

Maintenance

To Inspect and Replace the Evaporator Pad:

It is recommended that the evaporator pad in the humidifier be replaced annually to
maintain efficient operation. However, more frequent replacement may be necessary in
areas of poor water quality.

1. Disconnect the power supply to the furnace.Turn OFF the water supply at the saddle

valve by turning the valve handle clockwise.

2. Fully loosen the thumb screw at the bottom of the unit cover. The screw will remain

attached to the cover. To remove the cover from the duct, pull the bottom away and
then lift up. Put the cover aside for reassembly.

3. Remove the water distribution tray, located above the evaporator pad. It is held in place

by a snap that must be lifted to pull out the tray.

4. Pull the evaporator pad and frame assembly away from the duct, being careful not to

disturb the drain connection. Remove the old evaporator pad and discard.

5. Inspect the interior of the humidifier and remove any mineral deposits and accumulation

from the frame assembly and drain tray.

6. Remove the new evaporator pad from the plastic bag and insert into the frame assembly,

with the black spot facing up. Ensure that no part of the evaporator pad is outside of
the frame. Return the evaporator pad and frame assembly to their original position
inside the humidifier.

7. Check the distribution tray to ensure that holes are clear of any scale build up. If desired,

the distribution tray can be washed with mild detergent and warm water.

8. Replace the distribution tray making sure the snap is hooked over the outside edge of

the tray. Replace the cover and secure by tightening the thumb screw. Turn the water
back on and reconnect power to the furnace.

End of Heating Season Shut Down:

1. Inspect and clean humidifier and components.

2. Turn water supply off at the solenoid valve.

3. Turn humidistat off.

4. Close the bypass damper if installed.