Wiring, Subbase and base installation, Terminal designations – Honeywell EASY-TO-SEE T87N User Manual

Page 3

Advertising
background image

English:

Page 1 •

Français:

Page 6 •

Español:

Página 11

3

69-1840EFS—03

1. Pull wires through wire

hole. Position coverplate

on wall, level and mark hole

positions.

2. Drill holes (3/16” for drywall,

7/32” for plaster) and tap in

supplied wall anchors.

3. Pull wire through coverplate

and subbase, position over

anchors, then insert and

tighten mounting screws.

Check level if desired.

4. Apply the large-print labels

to the coverplate, matching

the labels on the subbase.

1. Loosen screw terminals, insert wires

into terminal block, then re-tighten

screws.

2. Push excess wire back into the wall

opening.

3. Plug the wall opening with

nonflammable insulation to prevent

drafts from affecting thermostat

operation.

Terminal Designations

W

Heat relay.

Y

Compressor contactor.

G

Fan relay.

O

Heat pump changeover valve
energized in cooling.

Rc Cooling power. Connect to

secondary side of cooling system
transformer.

R

Heating power. Connect to
secondary side of heating system
transformer.

B

Heat pump changeover valve
energized in heating.

Wiring

NOTES

R & Rc terminals
In single-transformer system, leave metal

jumper in place between

R

&

Rc

. Remove

metal jumper if two-transformer system.

Heat pump systems
If wiring to a heat pump, use a small piece
of wire (not supplied) to connect terminals W
and Y.

Wire specifications
Use 18- to 22-gauge thermostat wire.

Shielded cable is not required.

R

G

W

Y

B

Rc

O

E

F

Coverplate

Subbase

Large-print

subbase switch

labels

Subbase and base installation