Fan operation settings:
F: For gas or oil heating systems, leave

the fan operation switch in this factory-set

position (for systems that control the fan in

a call for heat).
E: Change the switch to this setting for heat

pump or electric heat systems. (This setting

is for systems that allow the thermostat

to control the fan in a call for heat, if a fan

wire is connected to the G terminal.)

Align the slots on the base with tabs on the

thermostat, then push gently until the

thermostat snaps into place.

E

F

Fan operation settings

Cycle rate settings

Thermostat mounting

Thermostat

Coverplate

and subbase

Heating System

Switch 1 Switch 2

Steam or gravity (1 CPH)

On

On

High efficiency warm air

Off

On

(90%+), hot water, or
heat pump (3 CPH)

Gas or oil warm air

Off

Off

(factory setting) (5 CPH)

Electric warm air (9 CPH)

On

Off

Move the cycle rate switches

to the proper setting for your

system (see table below).