Duct mounting – Honeywell H8908B Humidistat User Manual

Page 2

Advertising
background image

H8908B HUMIDISTAT H8908C DEHUMIDISTAT

69-1341

2

6.

Remove the H8908 case from the base. See
Fig. 1.

7.

Position the base on the wall with the arrow up.

8.

Use the two 1 in. (25 mm) mounting screws to
secure the base to the wall.

Fig. 2. Positioning mounting template.

IMPORTANT

Use 18- to 22-gauge wire for proper wiring.

9.

Connect the low voltage wires to the leads on the
H8908.

10.

Replace the H8908 case.

Duct Mounting

IMPORTANT

When mounting near an elbow area, locate the
control 6 in. (152 mm) upstream from the
elbow so the element is exposed to the normal
airflow (Fig. 3).

Fig. 3. Selecting duct location for control.

1.

Locate the control at least 8 in. (203 mm)
upstream from the humidifier (or dehumidifier/
ventilator supply) in the return air duct. See Fig. 3.

2.

Apply the duct template to the duct location.

3.

Use the duct template, Fig. 4, to make the open-
ing and mounting holes for the H8908.

4.

Remove the H8908 case from the base. See
Fig. 1.

5.

Position the foam gasket on the H8908 base.

6.

Position the base on the duct with the arrow up.

7.

Use the four 1 in. (25 mm) mounting screws to
secure the base to the duct.

8.

Connect the low voltage wires to the leads on the
H8908.

9.

Replace the H8908 case.

IMPORTANT

Use 18- to 22-gauge wire for proper wiring.

Fig. 4. Positioning return air duct template.

M13370

THERMOSTAT
WALLPLATE

MOUNTING
TEMPLATE

MOUNTING
HOLES (2)

WIRING HOLES FOR MOUNTING ON RIGHT.
USE LEFT HOLES FOR MOUNTING ON LEFT.

ALTERNATE LOCATION

RETURN
AIR

RETURN
AIR

6 in. (152 mm)
MINIMUM

15 in. (381 mm)
MINIMUM

BEST
LOCATION

RETURN AIR DUCT

M13369

CAUTION

Equipment Damage Hazard.
Be careful when selecting control
location and cutting hole in ductwork.
Do not cut or drill into air conditioning
or electrical accessories.
Do not install control on supply (hot air) ductwork.
To use template:
1. Remove backing and apply template to duct.
2. Cut along template dotted line and drill the

mounting holes.

4X DRILL 7/64 IN. DIAMETER
PERCER 4 X 7/64 PO.

MISE EN GARDE

Risque d'endommager le matériel.
Faire attention au moment de choisir
l'emplacement du régulateur et de percer les
trous dans la gaine.
Ne pas couper ou percer les accessoires
électriques ou de climatisation.
Ne pas installer le régulateur sur la gaine
d'alimentation (air chaud).
Utilisation du gabarit:
1. Retirer l'endos du gabarit et placer le gabarit

sur la gaine.

2. Couper le long de la ligne pointillée du gabarit

et percer les trous de fixation.

DUCT TEMPLATE

GABARIT DE GAINE

M13373

Advertising
This manual is related to the following products: