H8908B HUMIDISTAT H8908C DEHUMIDISTAT

3

69-1341

WIRING

CAUTION

Personal Injury Hazard.
Power supply can cause electrical shock and
injury.
Disconnect power supply before installation or
servicing.

All wiring must comply with applicable local codes, ordi-
nances and regulations. Make wiring connections
according to humidifier (or dehumidifier/ventilator)
instructions, if available; otherwise, see typical wiring
diagrams in Fig. 5 through 12.

IMPORTANT

Select models of fan centers include humidifer
taps so the current sensing relay or sail switch
is not needed.

If not using a current sensing relay or sail
switch, the humidifier must be energized dur-
ing blower motor cycles for proper operation.

On multispeed blower applications, do not wire
the high voltage side of the transformer to the
same power source that services the furnace
blower. Premature transformer burnout can
occur.

On HE360 fan powered humidifier models,
only the two yellow wires are connected to the
control. The remaining two red wires are only
used with electronic humidity controls.

Fig. 5. Typical wiring diagram for

system with fan interlock.

Fig. 6. Typical wiring diagram for system

with 2-speed fan motor.

Fig. 7. Typical wiring diagram of current

sensing relay with humidifier.

Fig. 8. Typical wiring diagram
of sail switch with humidifier.

Fig. 9. Typical wiring diagram for steam humidifiers.

Fig. 10. Typical parallel wiring of humidity controller

with Chronotherm® IV Thermostat for

dehumidification and mildew control.

1

1

2

PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION
AS REQUIRED.

24 VAC WIRING.

2

HUMIDIFIER

TRANSFORMER

FURNACE
FAN
MOTOR

H8908B

FAN CONTROL

L1
(HOT)

L2

M13368

POWER
SUPPLY

1

1

H

L

C

2

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.

24 VAC WIRING.

2

HUMIDIFIER

TRANSFORMER

2-SPEED
FAN
MOTOR

DPST
SWITCHING
RELAY

H8908B

FAN CONTROL

L1
(HOT)

L2

M13384

POWER
SUPPLY

M13386

L1
(HOT)

L2

1

2

1

2

POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.

24V WIRING.

HUMIDIFIER

TRANSFORMER

WATER
SOLENOID
LEAD WIRE

CURRENT
SENSING
RELAY

C

LO

HI

H8908B

M13385

L1
(HOT)

L2

1

2

1

2

POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.

24V WIRING.

HUMIDIFIER

TRANSFORMER

H8908B

SAIL
SWITCH

M13387

1

1

1

FOLLOW THE INSTALLATION INSTRUCTIONS
INCLUDED WITH THE STEAM HUMIDIFIER
TO WIRE THE SYSTEM FAN.

NOTE:

HUMIDIFIER

H8908B

TO
SYSTEM
FAN

HUMIDISTAT
TERMINALS

FAN WIRING
TERMINALS

24V WIRING.

B

O

W

Y

G

R

HEATING
RELAY OR
VALVE COIL

COOLING
CONTACTOR
COIL

FAN
RELAY
COIL

CHRONOTHERM® IV THERMOSTAT

PROVIDE OVERLOAD PROTECTION AND
DISCONNECT MEANS AS REQUIRED.

M13366

H8908C

1

1

Advertising