Set cycle rate switches – Honeywell CT87K User Manual

Page 4

Advertising
background image

CT87N/CT87K • Owner's Manual

69-1959EFS—02

4

1. Align the slots on the base with tabs on

the thermostat, then push gently until the

thermostat snaps into place.

2. Restore electrical power at the heating/

cooling system, or at the fuse/circuit-

breaker panel.

Move the switch to the proper setting for your

system:
F: For gas or oil heating systems, leave the

fan operation switch in this factory-set position

(for systems that control the fan in a call for

heat).
E: Change the switch to this setting for heat

pump or electric heat systems. (This setting

is for systems that allow the thermostat to

control the fan in a call for heat, if a fan wire is

connected to the G terminal.)

E

F

Set fan operation switch (CT87N)

Finish installation

Base

Heating System

Switch 1

Switch 2

Steam or gravity

On

On

High efficiency warm air

Off

On

(90% plus efficiency),
hot water, or heat pump
Gas or oil warm air

Off

Off

(factory setting)
Electric warm air

On

Off

Thermostat

Coverplate

(optional)

Move the cycle rate switches

to the proper setting for your

system (see table below).

Set cycle rate switches