ML6284 NON-SPRING RETURN DIRECT COUPLED DAMPER ACTUATOR

5

63-2505

Fig. 2. Installing mounting bracket on ML6284 Non-Spring

Return Direct Coupled Damper Actuator. NOTE: Install

mounting bracket so mounting bracket tab is centered in

actuator slot.

A typical actuator mechanical connection is shown in Fig. 4;

wiring diagrams in Fig. 5 through 10.

The ML6284 Non-Spring Return Direct Coupled Damper

Actuator can also be three-point mounted using the two front

gear housing slots and the adapter bracket. Two screws are

secured through the two front gear housing slots and the

adapter bracket positioned to secure the rear of the actuator.

Three point mounting is used for foot mounting the actuator or

internally mounting the actuator in the duct when direct shaft

coupling is not possible.

CAUTION

Equipment Damage Hazard.

Improper mounting will damage the actuator.

Do not use the actuator as a shaft bearing. The

actuator must be used only to supply rotational torque.

To prevent damage to the actuator, avoid any side

loads to the actuator output coupling bearings.

Preparation

Before installing the ML6284 on the damper shaft, determine

the opening direction of the damper shaft (see Fig. 2) to

correctly connect the wiring.

Installation

Installing Actuator and Mounting Bracket
(Single Point Mounting)

1. Place the ML6284 Non-Spring Return Direct Coupled

Damper Actuator over the damper shaft.

2. Position the actuator for best access to the actuator

damper shaft locking screw.

3. Install the mounting bracket (see Fig. 2) and adjust it so

the bracket tab is midway in the actuator slot. Mark the

screw holes for installing the mounting bracket on the

damper housing.

4. Remove the mounting bracket and actuator.

5. Drill or center punch the starting holes for the mounting

bracket screws (or use no.10 self-tapping sheet metal

screws—not supplied).

6. Place the actuator and mounting bracket back into

position over the damper shaft and install the mounting

bracket screws.

7. Move damper shaft either fully clockwise

or fully

counterclockwise

.

8. Fully depress and hold disengage button while moving

the actuator hub either fully clockwise

or fully

counterclockwise

to match the damper shaft.

Release disengage button.

9. Tighten the two 8 mm by 12 mm long set screws firmly

against the damper shaft (maximum tightening torque is

100 lb-in.).

Wiring

WARNING

Electrical Shock Hazard.

Can cause severe injury, death or property

damage.

Disconnect power supply before wiring to prevent

electrical shock or equipment damage.

All wiring must comply with local electrical codes, ordinances

and regulations. The ML6284 is designed for use with a Class

2 power supply. Voltage and frequency of the transformer

used must correspond with the characteristics of the motor

and those of the power supply. Standard electrical connection

is shown in Fig. 4. See Fig. 5 and 6 for typical wiring

connections.

The ML6284 has a plastic housing with two taped holes on

the end of the device for 1/2 in. conduit fittings.

ML6284 Models with Factory-mounted Auxiliary Switches

(See Fig. 7)

ML6284C,F models have two nonadjustable low voltage rated

spdt auxiliary switches that are factory set to make common to

normally open at 12° and 82° rotation from the closed

counter-clockwise stop. See Fig. 7.

M7876

ACTUATOR

SLOT