ML6284 NON-SPRING RETURN DIRECT COUPLED DAMPER ACTUATOR

Fig. 9. Common transformer with two controller outputs

and two ML6284D,F actuators.

Fig. 10. Common transformer with one controller output

and two ML6284A,C actuators.

CHECKOUT

Perform the following steps to checkout the ML6284

Non-Spring Return Direct Coupled Damper Actuator.

1. Check the actuator position indicator and the damper

shaft position to see that they agree.

2. If the actuator has time-out function, apply 24 Vac to

black (T1) lead and red (T2) lead. See Fig. 5.

3. Apply 24 Vac control signal to blue (B) lead with respect

to black (T1) lead (see Fig. 5). Actuator should drive

damper open.

4. Apply 24 Vac control signal to yellow (W) lead with

respect to black (T1) lead (see Fig. 5). Actuator should

drive damper closed.

5. If 24 Vac control signal is removed, actuator should

stop.

TROUBLESHOOTING

Perform the following troubleshooting steps if the actuator

does not drive, travel full stroke, or operate properly during the

checkout.

NOTE: Perform these steps before replacing the actuator.

1. Check the actuator label to verify that proper power and

control signal requirements have been met.

2. Check for 24 Vac at actuator black (T1), yellow (W) or

blue (B), and red (T2) [if actuator has time-out function]

leads when the actuator should be driving. If the voltage

is not present or is low, check power supply and

controller.

3. If the actuator does not drive in the correct direction

when a control signal is applied, reverse the yellow and

blue wires.

4. Remove power and fully depress and hold disengage

button down while turning damper shaft clockwise

and counterclockwise

. If the damper shaft turns

freely through the entire 90¡ stroke and the actuator is

installed correctly, replace the actuator.

5. If the damper shaft will not turn freely for the full 90°

check for any bind and make sure the actuator is loose

on the mounting bracket. If necessary, adjust mounting

bracket to prevent binding.

6. If no binding is noticed in the actuator and damper

assembly, remove the actuator and turn the damper

shaft clockwise

and counterclockwise

. If

the damper does not turn freely, repair or replace the

damper.

7. If the damper turns, fully depress and hold the actuator

disengage button down and turn the actuator hub

clockwise

and counterclockwise

. If the

actuator hub does not turn, replace the actuator.

8. If the actuator and damper turn freely, remount the

actuator to the damper in accordance with the

instructions in the Installation section. Make sure the

actuator and mounting bracket do not bind. Make sure

the actuator and damper are both at the same end stop

(clockwise

or counterclockwise

) when they

are assembled. Hook up the wires and repeat the

checkout. Troubleshoot again, if necessary.

L1

(HOT)

L2

1

1

RED
BLACK

RED

BLACK

ML6284D,F

ML6284D,F

M4886A

POWER SUPPLY. PROVIDE DISCONNECT MEANS

AND OVERLOAD PROTECTION AS REQUIRED.

CONTROLLER

CONTROLLER

BLUE

YELLOW

BLUE

YELLOW

L1

(HOT)

L2

1

1

BLACK

BLACK

ML6284A,C

ML6284A,C

M4887A

POWER SUPPLY. PROVIDE DISCONNECT MEANS

AND OVERLOAD PROTECTION AS REQUIRED.

CONTROLLER

BLUE

YELLOW

BLUE

YELLOW