Termination locations, Warning, A. vent termination minimum clearances – Hearth and Home Technologies B-Vent Gas Appliance CB4842MIR User Manual

Page 21

Advertising
background image

Heatilator • Caliber Mesh BV Series • 4040-848 Rev G • 10/08

21

A. Vent Termination Minimum Clearances

A Gas

Termination

Wood or Fuel Oil Termination

B 6

in.

(152 mm) min.

20 in.

(508 mm) min.

B-Vent Gas, Wood or Fuel

Oil Termination

8 ft

(2.44 m)

(minimum) to

Perpendicular

Wall

(BV only)

18 in.

(457 mm)

A

Gas

Termination

B

Termination Caps Staggered Height

B-Vent Gas, Wood or Fuel

Oil Termination

8 ft

(2.44 m)

(minimum) to

Perpendicular

Wall

(BV only)

Wood, Gas or

Fuel Oil

Termination

20 in. min. *

(508 mm)

Termination Caps Same Height

* If using decorative cap cover(s), this distance may
need to be increased. Refer to the installation instruc-
tions supplied with the decorative cap cover.

Figure 6.1 Minimum Height From Roof To Lowest Discharge
Opening

6

6

Termination Locations

Fire Risk.
Maintain vent clearance to combustibles as
specifi ed.

DO NOT pack air space with insulation

or other materials.

Failure to keep insulation or other materials away
from vent pipe may cause overheating and fi re.

WARNING

Figure 6.2 Termination Cap Clearances

12

X

8 ft

(2.44 m)

Lowest

Discharge

Opening

Termination

Cap

Roof Pitch
is X / 12

Vertical
wall

H (min.) - Minimum height
from roof to lowest
discharge opening.

Roof Pitch

H (Min.) Ft.

Roof Pitch

H (Min.) Ft.

Flat to 6/12

1.0*

Over 11/12 to 12/12

4.0

Over 6/12 to 7/12

1.25*

Over 12/12 to 14/12

5.0

Over 7/12 to 8/12

1.5*

Over 14/12 to 16/12

6.0

Over 8/12 to 9/12

2.0*

Over 16/12 to 18/12

7.0

Over 9/12 to 10/12

2.5

Over 18/12 to 20/12

7.5

Over 10/12 to 11/12 3.25

Over 20/12 to 21/12

8.0

* 3 ft. minimum in snow regions