Settings and calibration, Fig. 4—typical installations, Fig. 5—temperature settings – Honeywell T104F User Manual

Page 3

Advertising
background image

3

62-3047

Fig. 4—Typical installations.

M9734

18 INCH

MINIMUM

Settings and Calibration

The T104F Control includes an adjustable range limit-

ing pin (order additional pins separately). The pin is fac-
tory-set to limit the low range of the control to the frost
protection (*) setting (see Fig. 5). The pin can be moved to
a different low or high limit setting and lock point, or it can
be removed. Use a second pin if both low and high limit
settings are desired.

Setting the Limit

To set a limit different from the factory setting, proceed

as follows:

1. Determine the desired temperature range limit or lock-

ing temperature. Select the appropriate number on the ad-
justment knob to match the desired temperature setting. See
Fig. 5.

Fig. 5—Temperature settings.

M9729

SCALE MARKING

ADJUSTMENT RANGE SETTING

OFF

OFF

PIN
POS.

TEMP.

RANGE

°F

TEMP.

RANGE

°C

6

0

1

1

PIN REQUIRED.

FACTORY SETTING.

*

*

2

3

4

5

6

43

8

46

12

54

16

61

20

68

23

73

26

79

6 - 26

16 - 26

OFF - 26

20

22

0 - 20

6 - 20

0 - 23

6 - 23

43 - 79

61 - 79

OFF - 79

68

72

0 - 68

43 - 68

0 - 73

43 - 73

3

NONE

4a

4b

4b

4b + *

5 + *

5

°C

°F

2

2

1

1