Honeywell T104F User Manual

Page 4

Advertising
background image

62-3047

4

M9715

ADJUSTMENT
KNOB

END
CAP

ACTUATOR

2

3

2. Lift the end cap off the adjustment knob. See Fig. 6.

Fig. 6—Lift the end cap off the adjustment knob.

3. Remove the adjustment knob from the actuator as

follows:

a. Turn the adjustment knob so the desired knob setting

is aligned with the white line on the actuator base.

b. Pull the knob off the head or use a screwdriver inserted

into one of the slots to pry off the knob. See Fig. 7.

Fig. 7—Remove the knob from the actuator.

4. Push the limit pin up and slide it into the slot that

Locking the Control at a Single Temperature

1. Determine the desired locking temperature. Select the

appropriate number on the adjustment knob to match the
desired temperature setting. See Fig. 5.

2. Lift the end cap off the adjustment knob. See Fig. 6.
3. Remove the adjustment knob from the actuator as

follows:

a. Turn the adjustment knob so the desired knob setting

is aligned with the white line on the actuator base.

b. Pull the knob off the head or use a screwdriver inserted

in one of the slots to pry off the knob. See Fig. 7.

4. Insert the pin in slot 4a for 68

°F (20°C) or slot 4b for

72

°F (22°C).

Fig. 8—Insert the pin in the slot to set the limit
range.

5. To replace the adjustment knob, align the knob setting

from step 3a with the white line on the base and push the
knob toward the base. Make sure the three arm clips snap in
place at the top of the adjustment knob.

6. Replace the end cap.

Recalibrate T104F Control

1. Lift the end cap off the adjustment knob. See Fig. 6.
2. Pull the knob off the head or use a screwdriver inserted

in one of the slots to pry off the knob. See Fig. 7.

3. Turn the actuator head clockwise until the head stops

(Fig. 7). The calibration indent should be aligned approxi-
mately with the white line on the base when the head stops.
If the indent is 180 degrees from the white mark, unscrew the
head completely from the base and rethread the head to the
base so that it is aligned with the white mark. Turn the act-
uator head clockwise until the head stops. Complete removal
of the head from the base is required only if the actuator was
previously dismantled.

NOTE: The distance between the actuator head and the static

portion of the control should be approximately 3/8 in.
(9 mm).

4. Turn the actuator head counterclockwise approxi-

mately one turn until the calibration indent on the head aligns
with the white line on the base. For the 72

°F (22°C) single

temperature setting, align the indent with the center of the
adjustable limiting pin.

5. Replace the adjustment knob by aligning the red

button with the white line on the base and pushing the knob
toward the base. For the 72

°F (22°C) single temperature

setting, align the red button with the center of the adjustable
limiting pin. Make sure the three arm clips snap in place at
the top of the adjustment knob.

6. Replace the end cap.

corresponds with the desired temperature limit. If the lower
limit remains at the frost protection mark (*), insert an
additional pin in the slot that corresponds with the second
limit.

Example 1:

If the desired temperature range is 43

° to 73°F (6° to

23

°C), leave the pin in the slot marked * and add one pin in

slot 5.

Example 2:

If the desired temperature range is OFF to 68

°F (23 °C),

move the pin to slot 5. No additional pin is required.

5. To replace the adjustment knob, realign the knob

setting in step 3a with the white line on the base and push the
knob toward the base. Make sure the three arm clips snap into
place at the top of the adjustment knob. If the actuator was
turned with the adjustment knob off, recalibrate the control
according to the instructions in Recalibrate T104F Control
section.

6. Replace the end cap.

M9714

SCREWDRIVER SLOT (2)

WHITE LINE

RED
BUTTON

CALIBRATION
INDENT

ARM CLIP (3)

ACTUATOR HEAD

BASE

LIMIT PIN

LIMIT PIN REMOVED

WHITE LINE

FIXED STOP

PIN

POSITION

(SEE FIG. 5)

3

4a

4b

5

*

M9723

Advertising