Caution, Replacing clock with c or c1 clock terminals, Six or more wires – Honeywell CT2700 User Manual

Page 2: Remove old thermostat

Advertising
background image

69-1085

2

CT2700 AN ELECTRONIC ROUND

PROGRAMMABLE THERMOSTAT

Table 1. Compatibility Chart

Acquire tools and items as needed. See Fig. 1.

M878B

CROSS-RECESSED
SCREWDRIVER

HAND OR POWER
DRILL WITH 3/16 INCH
DRILL BIT, IF NEEDED TO
DRILL HOLES IN WALL

WIRE CUTTER/STRIPPER OR SHARP
KNIFE, IF NEEDED TO STRIP WIRES

MASKING TAPE, IF
NEEDED TO LABEL WIRES
AS DISCONNECTED FROM
OLD THERMOSTAT

LEVEL, IF NEEDED TO LEVEL
THERMOSTAT FOR APPEARANCE

Fig. 1. Required installation tools/supplies.

2

REMOVE OLD THERMOSTAT

Test to make certain that your heating and air
conditioning systems (where applicable) are working

properly. If either does not work, contact your local
heating/air conditioning dealer. To avoid compressor
damage, do not operate the cooling system when outdoor
temperature is below 50

°

F (10

°

C).

CAUTION

Be careful when handling wires during
installation.
Damage to heating/cooling system possible.
Disconnect power at furnace or at main breaker/
fuse box before starting operation.

Carefully unpack your new thermostat, wallplate,
and decorator cover plate; save package of screws,

instructions and receipt.

Remove the cover from the old thermostat. If it does
not snap off when pulled firmly from the bottom,

check for a screw used to lock on the cover.

Loosen screws holding thermostat to subbase,
wallplate, to wall and lift away.

Disconnect wires from old thermostat or subbase.
As you disconnect each wire, use masking tape to

label it with the old terminal designation. If there are only
two wires, they do not need labeling. Wrap wires around a
pencil to keep them from falling back into the wall as
shown in Fig. 2.

WIRES THROUGH
WALL OPENING

M5136

Fig. 2. Wrapping wires around pencil.

Replacing Clock With C or C1
Clock Terminals

If you are replacing a Honeywell Chronotherm® Thermo-
stat, you may find one or two wires that go to the C or C1
clock terminals on the Chronotherm®

Thermostat wiring

wallplate. Do not allow them to touch, or you can damage
your transformer. Disconnect the wires and wrap them
separately using electrical tape; do not wrap them
together. Place the wires to avoid interfering with the new
thermostat operation. Record the colors and terminal
designation labels of the remaining wires.

Six or More Wires

If there are six or more wires connected to the thermostat
(excluding clock wires attached to terminals), you probably
have a variation of a multistage heat pump or other
multistage system. The thermostat is not compatible with
such systems so return the product to your retailer. If you
would like information about which programmable
thermostats work with your system, call Honeywell
Customer Assistance Center at 1-800-468-1502.

System Type

Compatible With CT2700

Gas—Standing Pilot

Yes

a

Gas—Electronic Ignition

Yes

Gas-Fired Boilers

Yes

a,b

Gas—Millivolt

No

Oil-Fired Boilers

Yes

b

Oil-Fired Furnace

Yes

Electric Furnace

Yes

Electric Air Conditioning

Yes

Baseboard Electric (120/240 Line Volt)

No

Heat Pumps/Multistage Equipment

No

Not compatible with any 120/240 volt circuit.
Not compatible with 2-wire White-Rodgers no. 1361 zone valves.

a

Not compatible with millivolt systems.

b

Compatible with 2-wire Honeywell zone valves. Isolating relay required for 3-wire thermostats zone valves

Advertising