5.3.10 Checking WHP Controller Driver Chip

Diagram

Meter Set To Read DC Volts

Note: These tests assume that the controller being checked is powered up.

Overview

This check is intended to determine if the Comm Driver chip on a controller is damaged.
Damage typically occurs when the communications loop is exposed to excessive voltage, as
may occur during installation, due to wiring errors. The driver chips are socketed on all
boards to facilitate servicing. It is unusual for driver chips to fail during normal operation.
Almost all failures occur as a result of wiring related problems.

Measurements

Local Loop

Acceptable Range

T – SHLD

2.4 - 2.5 Volts DC

R – SHLD

2.4 - 2.5 Volts DC

Note: Minor variances may not indicate a problem if both tests indicate similar values.

Action

Condition

Action

If voltages are too high or too low on either
side

The controller has a damaged Comm
Driver chip. Replace the driver chip. See
"1.3.11 Comm Driver Chip Replacement”.