WattMaster WHP

Section 3

Programming

3-31

Setpoint Screen #12

Setpoint Screens #13

Note: Due to memory limitations in the Loop Controller, the maximum amount of

calibration offset is 10.0

°

F.

Setpoint Screen #14

Setpoint Screen #15

If you configured the system for Variable Speed Pumping with a
Pressure Sensor for proof of flow, the Loop Controller can send
a signal to all the Heat Pumps to open their Isolation Valves
whenever a Hi Limit Pressure is exceeded. If the Heat Pumps do
not control an Isolation Valve, then the only reaction is to
reduce the variable speed pump voltage signal.

WHP Loop Setpoints

Isolation Valves Set

Open if PSI is Above

Hi Limit...: xxx PSI

Minimum

Default

Maximum

Hi Limit

1 PSI

50 PSI

50 PSI

The Thermister Type III Sensor readings can be calibrated.
Enter a Positive value to increase the reading or a Negative
value to decrease the reading. If no sensor is attached, the
calibration offset will still allow a value to be input and read for
diagnostic purposes.

SENSOR CALIBRATION

RWT xxx.x

°

xxxx.x

°

°

SWT xxx.x

°

°

xxxx.x

°

°

OAT xxx.x

°

°

xxxx.x

°

°

Minimum Default Maximum

Return Water RWT

-10.0°F

0.0°F

+10.0°F

Supply Water SWT

-10.0°F

0.0°F

+10.0°F

Outdoor Air OAT

-10.0°F

0.0°F

+10.0°F

Alarms can be configured to light the LED on the front of the
System Manager by setting Alarms to Enabled, if you do not
wish to report alarms, select Disabled.

WHP Loop Setpoints

Alarms: Enabled

Use Left/Right Arrow

Use this screen to configure the relays on the expansion board
for heat ADDITION, REJECTION or NOT USED. All 8
relays come up one at a time.

WHP Loop Setpoints

Relay Configurations

Rly 1: ADDITION

Use Left/Right Arrow