Connecting the host computer – HP R2200 User Manual

Page 23

Advertising
background image

Installation 23

CAUTION: Do not set the Battery Charge Level switch to the down position without an ERM connected.

There is a risk of damaging the internal battery system of the UPS.

NOTE: DIP switch 4 is inactive and does not affect UPS operation regardless of the position.

NOTE: An asterisk (*) indicates the default setting.

Output voltage Input

voltage

range

DIP switch 1

DIP switch 2

DIP switch 3

DIP switch 4

R/T2200

NA/JPN/TW

N

120 V* (NA)

108–127 V Up

Up

Up*

Up

110 V

99–116 V Up

Down

100 V*

(JPN/TWN)

90–106 V Down

Up

120

V 108–127

V Down Down Down Down

R/T2200 INTL 230 V

20–7243 V Up

Up

Up*

Up

230 V* (INTL) 207–243 V Up

Down

220 V

198–233 V Down

Up

240

V 216–254

V Down Down Down Down

Connecting the host computer

CAUTION: Use only the computer interface cable supplied with the UPS to connect the communications

port to the host computer.

CAUTION: Using a USB to serial converter cable will damage the UPS.

Connect the UPS to a host computer using either the USB cable or the DB9 serial cable included with the

UPS. Install HP Power Manager software 4.1 or later on the host computer. See the HP website

(

http://www.hp.com/go/rackandpower

) to download the latest version of HP Power Manager.