ANTICIPATOR
SETTING LEVER

ANTICIPATOR
SCALEPLATE

M9616

Servicing The Thermostat

System on-length adjustment

NOTE: Not applicable on CT1503 Millivolt Heat

model.

If the thermostat seems to cycle the heating

system too fast or too slow, adjust the heating
system on-length by moving the anticipator
setting lever one indicator mark at a time (Fig. 6);
a higher setting will increase heating system on
length a lower setting will decrease heating
system on-length. Observe the heating system
operation after each adjustment.

The heat anticipator must be correctly set.

An incorrect setting can result in room tempera-
ture swings or burn out the anticipator, which
would void the thermostat warranty.

Fig. 6—Heat anticipator setting.

IMPORTANT:

Most hot water systems require

a setting of 1.3 times the valve current
rating.