CLASS 500 ADVANCED KWH/DEMAND METER

15

62-0304—05

NOTE: To change device ID, set single point at 46049 with data set to new device ID (e.g., 1 to 247).

To set date/time, set multiple points at 46025 for 4 points with data set to HHMM SSDW MMDD YYYY (DW=day of week).

To clear single meter kWh/kW, set single point at 41001 with data set to 0000 (similarly for 41003, 41005, 41007).

To clear multiple meter readings, set multiple point at 41001 for 8 points with data set to 0000's.

NOTE: Jumper J5 & J6 must be closed in order for kWh del/rec and kVARh del/rec to be cleared.

ITEM PM-I W

DATA

(SAMPLE)

DESCRIPTION

46001

8 504D 324B 0106 0421 0800 454D 4F4E 2020 Firmware version: PM 5K, Ver, Ver date/time,

Honeywell

R

46009

8 456E 6572 6779 204D 6574 6572 0000 0000 Device description: Honeywell Energy Meter

R

46017

8 1356 4503 0613 0300 0000 0000 0000 0000 Initialize device with date/time

W

46025

8 1356 4503 0613 0300 0000 0000 0000 0000 RTC date/time, will accept broadcast

command

R/W

46033

8 1356 4503 0527 0300 0000 0000 0000 0000 CPU date/time (7 bytes, rest is reserved for

other future formats)

R/W

46041

8 0001 0001 0000 0000 0000 0311 0020 1100

Group, location, Device ID number

R/W

46049

8 0041 0000 0000 0000 0000 0311 0020 1100

Dev. ID, Hookup, Serial numbers….

R/W

46057

8 0592 0007 0000 0000 0000 0000 0000 0000 Recorder info.: idr, dem. int., dem. win.,

dem. syn., timezone, DST…

R/W

46065

8 0101 0001 0D03 3531 1000 0320 0000 0000 Meter info.: SN1&2, pulse rate, Volt/Amp/

CTs, PF/mult1&2, CT, PT

R/W

46513

8 0000 0101 0000 0000 0000 0100 0000 0000 Flags L1

46521

8 0000 0000 0000 0000 0000 0000 0613 0316 Flags L2

46529

8 0000 0000 0000 0000 0000 0000 0000 0000 Flags L3

46537

8 0000 0000 0000 0000 0000 0000 0000 0000 Flags L4

Table 4. Honeywell Modbus point map