T775J ELECTRONIC REMOTE TEMPERATURE CONTROLLER

63-2248—4

3

Mounting:
Mounts on any suitable horizontal or vertical surface. (See
Fig. 5 for mounting hole locations.)

Dimensions:
See Fig. 1.

Display Resolution:
Sensed temperature and other operating parameters are
displayed via a liquid crystal display (LCD) with a resolution of
1

°

F or 1

°

C.

Accessories:

C7100C1003 Duct Mount Averaging Sensor*.
T7047C1090 Wall Mount Sensor Case.
107324A Bulb Holder, duct insertion.
121371A Copper Immersion Well.
121371E Stainless Steel Immersion Well.
107408 Heat Conduction Compound, 4 ounce.
C7043A1098 Case and Immersion Well.
203401B Waterproof Sensor.
203531A Panel Mounting Kit.
A775A1003 Sensor Simulator.
*Use of C7100C1003 decreases accuracy of T775 to

±

2

°

F

(

±

1

°

C).

Fig. 1. Approximate T775J dimensions in in. (mm).

INSTALLATION

When Installing this Product...

³

Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous
condition.

·

Check the ratings given in these instructions and on the
product to make sure the product is suitable for your
application.

»

Installer must be a trained, experienced service
technician.

¿

After installation is complete, check out the product
operation as provided in these instructions.

SELECT

SET

ENTER

M344C

3-13/16 (97)

4-3/4 (121)

8-1/2
(216)

5-7/32
(134)

1-1/4
(32)

1-1/4
(32)

2-3/8 (60)

7/8 (22) DIAMETER

CAUTION

Disconnect power before installation to prevent
electrical shock or equipment damage.

Location and Mounting

Mount the controller in any convenient interior location using
the two mounting holes provided. Mounting screws are not
included. Use controller dimensions in Fig. 1 as a guide.

Sensor Location

The 193987GA Sensor can be used up to 1000 ft (304m)
from the T775 using standard AWG 18/2 unshielded wire. If
longer than 25 feet in an electrically noisy environment, use
shielded cable. Locate the sensor on pipes, in immersion
wells, in wall-mounted cases or on a bulb holder.

Multiple sensors can be parallel-series wired to sense
average temperature in large spaces. In order to maintain
control accuracy, be sure the number of sensors parallel-
series wired is of the n2 power (i.e., 1, 4, 9, 16, etc). See
Fig. 2.

Fig. 2. Parallel-series wiring of sensors.

Sensor Mounting

Mount the sensor on a wall or panel for sensing space
temperature (Fig. 3); strap it to a pipe, or insert it into a well
(Fig. 4) for hot/cold water sensing; or tape it to a standard
cap or bulb holder for duct air sensing. To prevent moisture or
condensation entering the sensor through the leadwire holes,
mount the sensor with leadwires exiting the bottom of the
sensor.

NOTE:

Use heat conductive compound in immersion wells.
See Accessories.

TO T775 CONNECTIONS 1 AND 2 (SENSOR A)
OR 7 AND 8 (SENSOR B).

SENSORS

M7431