Appearance cause, Fig. 11. examples of unsatisfactory pilot flames – Honeywell S9371A User Manual

Page 16

Advertising
background image

S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS

Automation and Control Solutions
Honeywell International Inc.

Honeywell Limited-Honeywell Limitée

1985 Douglas Drive North

35 Dynamic Drive

Golden Valley, MN 55422

Toronto, Ontario M1V 4Z9

customer.honeywell.com

® U.S. Registered Trademark
© 2007 Honeywell International Inc.
69-2076—01 M.S. 10-07

Fig. 11. Examples of unsatisfactory pilot flames.

LAZY YELLOW FLAME

WAVING BLUE FLAME

NOISY LIFTING
BLOWING FLAME

HARD SHARP FLAME

SMALL BLUE FLAME

CHECK FOR LACK OF GAS FROM:

• CLOGGED ORIFICE FILTER

• CLOGGED PILOT FILTER

• LOW GAS SUPPLY PRESSURE

• PILOT ADJUSTMENT AT MINIMUM

CHECK FOR LACK OF AIR FROM:

• DIRTY ORIFICE

• DIRTY LINT SCREEN, IF USED

• DIRTY PRIMARY AIR OPENING,
IF THERE IS ONE

• PILOT ADJUSTMENT AT MINIMUM

CHECK FOR:

• EXCESSIVE DRAFT AT PILOT
LOCATION

• RECIRCULATING PRODUCTS
OF COMBUSTION

CHECK FOR:

• HIGH GAS PRESSURE

THIS FLAME IS CHARACTERISTIC
OF MANUFACTURED GAS

CHECK FOR:

• HIGH GAS PRESSURE

• ORIFICE TOO SMALL

M3272A