4

Table 3. Approximate Weights

ACTUATOR SIZE

kg

lbs

EDA

ESA

EDA

ESA

E25

1.2

1.7

2.7

3.7

E40

1.8

2.4

4.0

5.3

E65

2.4

3.6

5.3

7.9

E100

2.8

4.6

6.1

10.1

E200

5.8

9.1

12.8

20.1

E350

10.4

16.9

22.9

37.3

E600

19.4

27.6

42.8

60.8

E900

26.4

38.6

58.2

85.0

E1600

42.7

65.8

94.1

145

P2500/P2505

56.7

88.0

125

194

P4000/P4005

86.2

132.0

190

291

Table 4. Bolting Torques between 1035 and Yoke

ACTUATOR SIZE

Bolt Diameter, Inches

Torque, NSm

Torque, lbfSft

E25

1/4

11

8.3

E40
E65

E100

5/16

22

16.5

E200
E350

3/8

39

29

E600

1/2

91

67

E950

5/8

163

120

E1600

3/4

258

190

P2500/P2505
P4000/P4005

3/4

203

150

Installation

When an actuator and a valve are shipped together, the actuator is normally mounted on the valve. Follow the valve

body instructions when installing the control valve in the pipeline. If the actuator is shipped separately from the valve

or if it is necessary to mount the actuator on the valve, perform the procedures in the Actuator Mounting section.

WARNING

Always wear protective gloves, clothing, and eyewear when performing any installation operations to avoid personal

injury.
To avoid personal injury or property damage caused by bursting of pressure-retaining parts, be certain the service

conditions do not exceed the limits given in table 1. Use pressure-limiting devices or pressure-relieving devices to prevent

the cylinder pressure from exceeding these limits.
If hoisting the valve and actuator assembly or the actuator by itself, take precautions to prevent people from being injured

in case the hoist or sling slips unexpectedly. Refer to table 3 for actuator weights. Carefully position the sling to prevent

damage to tubing or any accessories.
Check with your process or safety engineer for any additional measures that must be taken to protect against process

media.
If installing into an existing application, also refer to the WARNING at the beginning of the Maintenance section in this

instruction manual.