ED, ET, EZ, HP, HPA Valves w/ 657/667 Actuator

SIL Safety Manual

July 2010

7

Appendix A

Sample Startup Checklist

This appendix provides a Sample Start-up Checklist
for a Fisher ED, ET, EZ, HP, or HPA valve. A
start-up checklist will provide guidance during the
final control element’s emplo

yment.

Start

-Up Checklist

The following checklist may be used as a guide to
employ the ED, ET, EZ, HP, or HPA valve in a safety
critical SIF compliant to IEC61508.

#

Activity

Result

Verified

By

Date

Design

Target Safety Integrity Level and PFD

AVG

determined

Correct valve mode chosen (Fail-closed, Fail-open)

Design decision documented

Pneumatic compatibility and suitability verified

SIS logic solver requirements for valve tests defined and
documented

Routing of pneumatic connections determined

SIS logic solver requirements for partial stroke tests defined and
documented

Design formally reviewed and suitability formally assessed

Implementation

Physical location appropriate

Pneumatic connections appropriate and according to applicable
codes

SIS logic solver valve actuation test implemented

Maintenance instructions for proof test released

Verification and test plan released

Implementation formally reviewed and suitability formally assessed

Verification and Testing

Electrical connections verified and tested

Pneumatic connection verified and tested

SIS logic solver valve actuation test verified

Safety loop function verified

Safety loop timing measured

Bypass function tested

Verification and test results formally reviewed and suitability formally
assessed

Maintenance

Tubing blockage / partial blockage tested

Safety loop function tested